Table 35 — User Defined Set Points

LEGEND

Table 36 — Software Control Link Points

LEGEND

SET POINT

NAME

FORMAT

DESCRIPTION

LIMITS

DEFAULT

OHSP

xx.xF

Occupied Heat Set Point

55 to 80 F

68 F

OCSP

xx.xF

Occupied Cool Set Point

55 to 80 F

78 F

UHSP

xx.xF

Unoccupied Heat Set Point

35 to 80 F

55 F

UCSP

xx.xF

Unoccupied Cool Set Point

75 to 110 F

90 F

SASP

xx.xF

Supply Air Set Point

45 to 70 F

55 F

OATL

xx.xF

Hi OAT Lockout Temperature

55 to 75 F

65 F

NTLO

xx.xF

Unoccupied OAT Lockout Temperature

40 to 70 F

50 F

RTIO

xx.x

Reset Ratio

0 to 10

3

LIMT

xx.xF

Reset Limit

0 to 20° F

10° F

MDP

xxx%

Minimum Damper Position

0 to 100%

20%

LOWMDP

xxx%

Low Temperature Minimum
Damper Position Override

0 to 100%

100%

IAQS

xxxx

IAQ Set Point

1 to 5000 PPM

650 PPM

UHDB

xx.xF

Unoccupied Heating Deadband

0 to 10° F

1° F

UCDB

xx.xF

Unoccupied Cooling Deadband

0 to 10° F

1° F

LTMP

xxx%

Low Temp. Min. Position

0 to 100%

10%

HTMP

xxx%

High Temp. Min. Position

0 to 100%

35%

PES1

xxx%

CV Power Exhaust Stage 1 Point

0 to 100%

25%

PES2

xxx%

CV Power Exhaust Stage 2 Point

0 to 100%

75%

CV

Constant Volume

IAQ

Indoor Air Quality

OAT — Outdoor-Air Temperature

SET POINT

DESCRIPTION

SET POINT

DESCRIPTION

CV Data

SPT

Space Temperature

HS2

Heat Stage 2

SAT

Supply-Air Temperature

STO

Space Temp. Offset

RAT

Return-Air Temperature

CVPE1

CV Power Exhaust Stg 1

OAT

Outside-Air Temperature

CVPE2

CV Power Exhaust Stg 2

CLSP

Control Set Point

VAV Data

CCAP

Cooling % Total Capacity

HIR

Heat Interlock Relay

HCAP

Heating % Total Capacity

SPTRESET

Space Temp. Reset

ECOS

Economizer Active

CMP1

Compressor 1

SFSTAT

Supply Fan Status

CMP1SAFE

Compressor 1 Safety

SF

Fan Relay

CMP2

Compressor 2

ECONPOS

Economizer Position

CMP2SAFE

Compressor 2 Safety

IQMP

Min. Damper Position

ULD1

Unloader 1

PEXE

Power Exhaust Enable

ULD2

Unloader 2

FLTS

Filter Status

OFC1

Outdoor Fan 1

FAS

Field Applied Status

OFC2

Outdoor Fan 2

RMTOCC

Remote Occupied Mode

Y1

Y1 — Call for Cool 1

General Data

Y2

Y2 — Call for Cool 2

HS1

Heat Stage 1

W1

W1 — Call for Heat 1

ENTH

Enthalpy

W2

W2 — Call for Heat 2

IAQI

Indoor Air Quality

G

G — Call for Fan

IAQO

Outdoor Air Quality

CDEVCODE

CONQUEST DEVICE CODE

SATRES

SAT Reset

CDEVURST

CONQUEST UNIT RESET

ALMLIGHT

Alarm Warning Light

CDEVBCAK

CONQUEST BROADCAST ACK

DL

Demand Limit Switch

PE1

Mod. Power Exhaust Stg 1

EVAC

Evacuation

PE2

Mod. Power Exhaust Stg 2

PRES

Pressurization

PE3

Mod. Power Exhaust Stg 3

PURG

Smoke Purge

PE4

Mod. Power Exhaust Stg 4

FSD

Fire Shutdown

PE5

Mod. Power Exhaust Stg 5

PE6

Mod. Power Exhaust Stg 6

CV

Constant Volume

VAV — Variable Air Volume