48DD

Gas Heating 275,000 Btuh

Electric Cooling 124,000 Btuh

48DD012

DESCRIPTION

The 48DD012 is a one-piece combination gas heating/

electric cooling unit designed primarily for outdoor rooftop

installation on a factory-supplied curb accessory but can be
installed on grade or conventional steel framework. This

unif combines superior performance with compactness,
versatility of application and ease of installation to supply
year-round air conditioning for commercial and industrial

buildings The unit is completely factory assembled,
charged and tested Requires only natural gas, and suitable
electrical and duct connections for hookup. Air can be
supplied to the building either thru bottom of the unit or
thru the side A manually-adjustable outdoor air intake is
provided Condensers are air cooled Low silhouette design
allows units to be easily hidden from street level view

FEATURES

Two-Stage Heating and Cooling — Both heating and

cooling stages have 50 percent or 100 percent capacity
ranges of operation This reduces operating costs

Multiple Choice of Air Flow — Air can be delivered to

the building either thru the bottom of the unit with
separate inlet and outlet air ducts or concentric ducting, or

it can be delivered thru the side of the unit with separate
inlet and outlet air ducts

Gas Safety Control will shut off the main gas valve in

case of pilot or combustion air failure, or overheating of the
heat exchangers

Induced Draft Combustion — Unaffected by winds and

drafts Equipped with safety shut-off devices in case of
combustion air failure or blockage

Automatic Electric Ignition — Pilot flame is auto­

matically relighted in case of interruption of power or gas

Aluminized Heat Exchangers — Resist corrosion and

provide long, quiet, safe, and efficient operation These
heat exchangers have a full ten-year warranty

Time Guard Circuit* prevents rapid cycling, extends

compressor life When power to unit is interrupted,
compressor cannot restart for five minutes

Head Pressure Control automatically cycles one of two

condenser fans, permitting cooling operation down to 35 F
ambient temperature

Other Quality Components — Crankcase heaters and

accumulators to protect the compressor against flooded
starts, filter-driers and sight glasses for moisture control and
visual inspection of refrigerant charge

ACCESSORIES

32LM MotormasterTM Head Pressure Control

mod­

ulates speed of condenser fan motor to maintain saturated
condensing temperature at low outdoor temperatures

Thermostat Assembly is a two-step heating/two-step

cooling thermostat and a matching switch base Either
automatic or manual changeover is available

Remote Control Center allows manual control of the

unit from a location remote from the thermostat The
thermostat furnished with the remote control center has no

knobs or switches for manual control

Roof Curb frames roof opening, is watertight connec­

tion between unit and roof Designed so ductwork and roof
flashing may be installed prior to placing the unit

Modulating Outside Air Control Package (economizer)

can furnish outside air for cooling when outside air

temperature is below 60 F. It can replace operation of the

refrigerant system under these conditions

LP Conversion Kit used to convert the unit from natural

gas to LP gas usage

Relief Damper used to relieve positive building pressure

© Carrier Corporation 1970

•Single Feature Sheet Available

Form 48DD-1 P