Carrier 48AJ User Manual
Page 75
75
Table 29 — Fan Performance, 48EJ,EK048 — Vertical Discharge Units
(For EW,EY units, reduce net available external static pressure by 0.5 in. wg)
LEGEND
Bhp — Brake Horsepower
NOTES:
1. Fan performance is based on wet coils, economizer, roof curb,
cabinet losses, and clean 2-in. filters.
2. Conversion — Bhp to watts:
3. Variable Air Volume units will operate down to 70 cfm/ton. Per-
formance at 70 cfm/ton is limited to unloaded operation and
may be additionally limited by edb (entering dry bulb) and ewb
(entering wet bulb) conditions.
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
9,000
528
3.20
572
4.00
615
4.40
656
4.90
695
5.30
733
5.80
769
6.20
805
6.70
10,000
577
4.10
617
5.10
657
5.50
694
6.00
731
6.40
766
6.90
801
7.40
834
7.90
11,000
627
5.10
664
6.30
700
6.80
735
7.30
769
7.70
802
8.20
835
8.70
866
9.20
12,000
677
6.30
711
7.70
745
8.20
778
8.70
809
9.20
841
9.70
871
10.20
901
10.80
13,000
728
7.71
760
9.31
791
9.83
822
10.35
851
10.88
881
11.42
909
11.95
938
12.50
14,000
779
9.28
809
11.11
838
11.65
867
12.20
895
12.75
923
13.31
950
13.87
976
14.43
15,000
830
11.03
858
13.13
886
13.69
913
14.26
939
14.83
966
15.41
991
15.99
1017
16.57
16,000
882
12.97
908
15.36
934
15.95
960
16.54
985
17.13
1010
17.73
1034
18.33
1058
18.93
17,000
934
15.12
959
17.83
983
18.44
1008
19.05
1031
19.66
1055
20.28
1078
20.89
1101
21.52
18,000
986
17.47
1010
20.53
1033
21.16
1056
21.79
1078
22.42
1101
23.06
1123
23.70
1145
24.34
19,000
1038
20.05
1061
23.49
1083
24.13
1105
24.78
1126
25.44
1147
26.09
1169
26.75
1190
27.41
20,000
1091
22.84
1112
26.69
1133
27.36
1154
28.03
1174
28.70
1195
29.37
—
—
—
—
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.8
2.0
2.2
2.4
2.6
2.8
3.0
3.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
9,000
839
7.10
873
7.62
905
8.10
937
8.59
968
9.08
999
9.57
1028
10.08
1057
10.58
10,000
866
8.40
898
8.85
929
9.34
959
9.85
989
10.36
1018
10.87
1047
11.39
1075
11.91
11,000
897
9.70
927
10.24
956
10.76
985
11.28
1013
11.81
1041
12.34
1068
12.87
1095
13.41
12,000
930
11.30
958
11.82
986
12.36
1014
12.90
1041
13.44
1067
13.99
1093
14.54
1119
15.10
13,000
965
13.04
992
13.59
1019
14.15
1045
14.71
1071
15.27
1096
15.84
1121
16.41
1146
16.98
14,000
1002
14.99
1028
15.56
1054
16.14
1079
16.71
1103
17.30
1127
17.88
1151
18.47
1175
19.06
15,000
1041
17.15
1066
17.74
1090
18.34
1114
18.93
1138
19.53
1161
20.13
1184
20.74
—
—
16,000
1082
19.52
1105
20.14
1128
20.75
1151
21.37
1174
21.99
1196
22.61
—
—
—
—
17,000
1124
22.14
1146
22.77
1168
23.40
1190
24.03
—
—
—
—
—
—
—
—
18,000
1166
24.98
1188
25.63
—
—
—
—
—
—
—
—
—
—
—
—
19,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
20,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
3.4
3.6
3.8
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
9,000
1086
11.10
1114
11.61
1141
12.14
10,000
1102
12.44
1129
12.97
1155
13.51
11,000
1122
13.96
1147
14.51
1173
15.06
12,000
1144
15.66
1169
16.23
1194
16.80
13,000
1170
17.56
1194
18.14
—
—
14,000
1198
19.66
—
—
—
—
15,000
—
—
—
—
—
—
16,000
—
—
—
—
—
—
17,000
—
—
—
—
—
—
18,000
—
—
—
—
—
—
19,000
—
—
—
—
—
—
20,000
—
—
—
—
—
—
Watts =
Bhp x 746
Motor Efficiency