APPENDIX A

A-2

APPENDIX A - BOILER MENU ITEM DESCRIPTIONS - Continued

MENU LEVEL & OPTION

DESCRIPTION

SETUP MENU

Password

Allows password to be entered.
Once the valid password (159) is entered, options in

the Setup, Configuration and Tuning Menus can be

modified.

Language

English only

Time

Displays time from 12:00 am to 11:59 pm.

Date

Displays dates from 01/01/00 to 12/31/99

Unit of Temp

Permits selection of temperature displays in degrees

Fahrenheit (°F) or degrees Celsius (°C). Default is

°F.

Comm Address

For RS-485 communications (0 to 127). Default

address is 0. RS-232 should have its own

(programmable) password.

Baud Rate

Allows communications Baud Rate to be set (2400

to 19.2K). Default is 9600.

Software Version

Identifies the current software version of the control

box (Ver 0.0 to Ver 9.9).

CONFIGURATION MENU

Internal Setpoint

Allows internal setpoint to be set . Default is 130°F.

Unit Type

Allows selection of KC Boiler, KC Boiler LN, BMK

Boiler, BMK Boiler LN, BMK Boiler Dual, KC Water

Heater, KC Water Heater LN, Water Heater 2010.

Default is BMK Boiler Dual.

Unit Size

Sets unit size from 0.5 to 6.0 MBTUs. Default is 3.0

MBTU.

Fuel Type

Allows selection of Natural Gas or Propane. Default

is Natural Gas.

Boiler Mode

It allows selection of: Constant Setpoint, Remote

Setpoint, Direct Drive, Combination, or Outdoor

Reset Mode. Default is Constant Setpoint Mode.

Remote Signal

Used to set the type of external signal which will be

used when operating in the Remote Setpoint, Direct

Drive or Combination Mode. The factory default is

4-20 mA/1-5V.

Bldg Ref Temp

Allows the building reference temperature to be set

when operating a boiler in the Outdoor Reset Mode.

Default is 70°F.