CONTROL PANEL OPERATING PROCEDURES

3-6

Table 3-3. Setup Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Passsword

0

9999

0

Language

English

English

Time

12:00 am

11:59 pm

Date

01/01/00

12/31/99

Unit of Temp

Fahrenheit or Celsius

Fahrenheit

Comm Address

0

127

0

Baud Rate

2400, 4800, 9600, 19.2K

9600

Software

Ver 0.00

Ver 9.99

3.6 CONFIGURATION MENU

The Configuration Menu shown in Table 3-4

permits adjustment of the Internal Setpoint

(Setpt) temperature regardless of whether the

valid password has been entered. Setpt is

required for operation in the Constant Setpoint

mode. The remaining options in this menu

require the valid password to be entered, prior to

changing existing entries. This menu contains a

number of other configuration settings which

may or may not be displayed, depending on the

current operating mode setting.

NOTE

The Configuration Menu settings shown in

Table 3-4 are Factory-Set in accordance

with the requirements specified for each

individual order. Therefore, under normal

operating conditions, no changes will be

required.

Table 3-4. Configuration Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Internal Setpt

Lo Temp Limit

Hi Temp Limit

130°F

Unit Type

KC Boiler, KC Boiler LN,

BMK Boiler, BMK Boiler LN,

BMK Boiler Dual, KC Water

Heater, KC Water Heater LN,

Water Heater 2010

BMK Boiler

Dual

Unit Size

0.5 MBTU, 1.0 MBTU

1.5 MBTU, 2.0 MBTU

3.0 MBTU, 3.5 MBTU

4.0 MBTU, 5.0 MBTU

6.0 MBTU

3.0 MBTU

Fuel Type

Natural Gas, Propane

Natural Gas

Boiler Mode

Constant Setpoint,

Remote Setpoint,

Direct Drive

Combination

Outdoor Reset

Constant

Setpoint