beautypg.com

8 interlock tests, 1 remote interlock, 2 delayed interlock – AERCO BMK 3.0 LN Dual-Fuel Series Gas Fired Low NOx Boiler System User Manual

Page 52: 9 flame fault tests, Safety device testing

background image

SAFETY DEVICE TESTING

6-4

6.8 INTERLOCK TESTS

The unit is equipped with two interlock circuits

called the Remote Interlock and Delayed

Interlock. Terminal connections for these circuits

are located in the I/O Box (Figure 2-9) and are

labeled REMOTE INTL’K IN and DELAYED

INTL’K IN. These circuits can shut down the

unit in the event that an interlock is opened.

These interlocks are shipped from the factory

jumpered (closed). However, each of these

interlocks may be utilized in the field as a remote

stop and start, an emergency cut-off, or to prove

that a device such as a pump, gas booster, or

louver is operational.

6.8.1 REMOTE INTERLOCK

1. Remove the cover from the I/O Box and

locate the REMOTE INTL’K IN terminals.

2. Start the unit in the Manual Mode and set

the valve position between 25% and 30%.

3. If there is a jumper across the REMOTE

INTL’K IN terminals, remove one side of the

jumper. If the interlock is being controlled by

an external device, either open the interlock

via the external device or disconnect one of

the wires leading to the external device.

4. The unit should shut down and display

INTERLOCK OPEN.

5. Once the interlock connection

is

reconnected, the INTERLOCK OPEN

message should automatically clear and the

unit should restart.

6.8.2 DELAYED INTERLOCK

1. Remove the cover from the I/O Box and

locate the DELAYED INTL’K IN terminals.

2. Start the unit in the Manual Mode at a valve

position between 25% and 30%.

3. If there is a jumper across the DELAYED

INTL’K IN terminals, remove one side of the

jumper. If the interlock is connected to a

proving switch of an external device,

disconnect one of the wires leading to the

proving switch.

4. The unit should shut down and display a

DELAYED INTERLOCK OPEN fault

message. The

FAULT LED should be

flashing.

5. Reconnect the wire or jumper removed in

step 3 to restore the interlock.

6. Press the

CLEAR button to reset the fault

7. The unit should start.

6.9 FLAME FAULT TESTS

Flame faults can occur during ignition or while

the unit is already running. To simulate each of

these fault conditions, proceed as follows:
1. Set the

ON/OFF switch to the OFF position.

2. Place the unit in the Manual Mode and set

the valve position between 25% and 30%.

3. Close the manual gas shutoff valve located

between the Safety Shut-Off Valve (SSOV)

and the Air/Fuel Valve (see Figure 6-3).

4. Set the

ON/OFF switch to the ON position to

start the unit.

5. The unit should shut down after reaching the

Ignition cycle and display FLAME LOSS

DURING IGN.

6. Open the valve previously closed in step 3

and press the

CLEAR button.

7. Restart the unit and allow it to prove flame.
8. Once flame is proven, close the manual gas

valve located between the SSOV and the

Air/Fuel Valve.

9. The unit should shut down and display

FLAME LOSS DURING RUN.

10. Open the valve previously closed in step 8.
11. Press the

CLEAR button. The unit should

restart and fire.