INITIAL START-UP

4-9

47. Press the

▼ arrow key until CAL Voltage

18% is displayed.

48. Press the

CHANGE key. CAL Voltage 18%

will begin to flash.

49. The oxygen level at the 18% valve position

should be as shown below. Also, ensure that

the carbon monoxide (CO) and nitrogen

oxide (NOx) readings do not exceed the

values shown.

Combustion Oxygen Level at

18% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

5.5 %

<100 ppm

<100 ppm


50. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼

arrow keys. This will adjust the output

voltage to the blower motor as indicated on

the display. Pressing the ▲ arrow key

increases the oxygen level and pressing the

▼ arrow key decreases the oxygen level.

51. Once the oxygen level is within the specified

range at 18%, press the

ENTER key to store

the selected blower output voltage for the

16% valve position.

52. This completes the Propane Combustion

Calibration procedure.

4.5 UNIT REASSEMBLY

Once the combustion calibration adjustments

are properly set for Natural Gas and Propane,

the unit can be reassembled for service

operation.
1. Access the Control Panel Configuration

Menu and ensure that the Max Valve

Position is set to the desired level for the

fuel being used for service operation (100%

for Natural Gas; 75% for Propane).

2. Set the control panel

ON/OFF switch to the

OFF position.

3. Disconnect AC power from the unit.
4. Shut off the gas supply to the unit.
5. Set the Fuel Selector Switch to the

corresponding position for the fuel being

used for service operation.

6. Remove the manometer and barbed fittings

and reinstall the NPT plug using a suitable

pipe thread compound.

7. Remove the combustion analyzer probe

from the vent hole. Replace the NPT plug in

the vent hole using a suitable pipe joint

compound.

8. Replace the unit’s side panels and front

door.

4.6 OVER-TEMPERATURE LIMIT

SWITCHES

The unit contains both automatic and manual

reset over-temperature limit switches. These

switches are mounted on a plate attached to the

boiler shell as shown in Figure 4-7. The switches

can be accessed by removing the left side

panels of the unit. The manual reset switch is

not adjustable and is permanently fixed at

200°F. This switch will shut down and lock out

the boiler if the water temperature exceeds

200°F. Following an over-temperature condition,

it must be manually reset by pressing the

RESET button before the boiler can be

restarted. The automatic reset over-temperature

switch is adjustable and allows the boiler to

restart, once the temperature drops below its

temperature setting. Set the automatic over-

temperature switch to the desired setting.

RESET BUTTON FOR MANUAL

RESET TEMPERATURE LIMIT

SWITCH

ADJUSTABLE

TEMPERATURE

LIMIT SWITCH

MOUNTING

PLATE

ON SHELL

HIGH LIMIT

Figure 4-7

Over Temperature Limit Switch

Locations