CHAPTER 3: CONTROL PANEL OPERATION

PR2: 04/22/13 Page 39 of 160


Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

25

TO BLOWER

AIR IN

DIAL
(DETAIL “A”)

STEPPER

MOTOR

DETAIL “A”

Figure 3-6: Air/Fuel Valve In Ignition Position

6. Up to 7 seconds will be allowed for ignition to be detected. The igniter relay will be

turned off one second after flame is detected.

7. After 2 seconds of continuous flame, Flame Proven will be displayed and the flame

strength will be indicated. After 5 seconds, the current date and time will be displayed
in place of the flame strength.

8. With the unit firing properly, it will be controlled by the temperature controller circuitry.

The boiler’s VALVE POSITION will be continuously displayed on the front panel
bargraph.

Once the demand for heat has been satisfied, the Control Box will turn off the dual SSOV
gas valves. The blower relay will be deactivated and the Air/Fuel Valve will be closed.
Standby will be displayed.

3.10 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the
unit, based on load. These levels are Factory preset as follows:

Natural Gas

Propane

Start Level:

25%

25%

Stop Level:

20%

21%

Normally, these settings should not require adjustment.