8

-

5

TABLE 8-1. BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

TROUBLESHOOTING/CORRECTIVE ACTION

(continued) 8.

Defective staged ignition solenoid
valve.

9. Clogged staged ignition piece.

10. Carbon or other debris on burner

8. When boiler goes to ignition, listen to solenoid valve to ensure it

is opening.

9.

Remove and inspect staged ignition piece for blockage.

Remove the burner and inspect for any carbon or debris. Clean
and reinstall

FLAME LOSS

DURING RUN

1. Worn Flame Detector or cracked

ceramic.

2. Poor combustion calibration.

3. Debris on burner.

4. Blocked condensate drain.

1. Remove and inspect the Flame Detector for signs of wear or

cracked ceramic. Replace if necessary.

2. Check combustion calibration. Adjust as necessary.

3. Remove the burner and inspect for any carbon or debris. Clean

and reinstall.

4. Remove blockage in condensate drain.

HEAT DEMAND

FAILURE

1. The Heat Demand Relays on the

Ignition/Stepper board failed to
activate when commanded

2. Relay is activated when not in

Demand

1. Press CLEAR button and restart the unit. If the fault persists,

replace Ignition/Stepper (IGST) Board.



2. Defective relay. Replace IGST Board.

HIGH GAS

PRESSURE

1. Incorrect supply gas pressure.

2. Defective gas pressure adjustment

in SSOV Actuator.

1. Check to ensure gas pressure at inlet of SSOV is 2 psig

maximum.

2. If gas supply pressure downstream of SSOV cannot be lowered,

to 2.8” W.C. (or 2.3" W.C. for propane), the SSOV Actuator gas
pressure adjustment mechanism may be defective. [see para.
4.3, step 10 (natural gas), or 4.4, step 10 (propane)],