beautypg.com

7 flame fault tests, 8 air flow fault tests, Safety device testing – AERCO BMK 2.0 LN Nat. Gas June 2010 User Manual

Page 54

background image

SAFETY DEVICE TESTING

6. Press

the

CLEAR

button to reset the fault

7. The unit should start.

6.7 FLAME FAULT TESTS

Flame faults can occur during ignition or while
the unit is already running. To simulate each of
these fault conditions, proceed as follows:

1. Set

the

ON/OFF

switch to the OFF position.

2. Place the unit in the Manual Mode and set

the valve position between 25% and 30%.

3. Close the manual gas shutoff valve located

between the Safety Shut-Off Valve (SSOV)
and the Air/Fuel Valve (see Figure 6-3).

4. Set

the

ON/OFF

switch to the ON position to

start the unit.

5. The unit should shut down after reaching the

Ignition cycle and display FLAME LOSS
DURING IGN.

6. Open the valve previously closed in step 3

and press the CLEAR button.

7. Restart the unit and allow it to prove flame.

8. Once flame is proven, close the manual gas

valve located between the SSOV (Figure 6-
3) and the Air/Fuel Valve.

9. The unit should shut down and execute an

IGNITION RETRY

cycle by performing the

following steps:

(a) The unit will execute a shutdown purge

cycle for a period of 15 seconds and
display WAIT FAULT PURGE.

(b) The unit will execute a 30 second re-

ignition delay and display WAIT RETRY
PAUSE.

(c) The unit will then execute a standard

ignition sequence and display WAIT
IGNITION RETRY

.

10. Since the manual gas shutoff valve is still

closed, the unit will shut down and display
FLAME LOSS DURING IGNITION

following

the IGNITION RETRY cycle.

11. Open the valve previously closed in step 8.

12. Press the CLEAR button. The unit should

restart and fire.

Figure 6-3

Manual Gas Shut-Off Valve Location

6.8 AIR FLOW FAULT TESTS

These tests check the operation of the Blower
Proof Switch and Blocked Inlet Switch shown in
Figure 6-3.

1. Disable the blower output drive voltage as

follows:

(a) Press the MENU key until CONFIGUR-

ATION MENU

is displayed.

(b) Press

the

▲ arrow key until the ANA-

LOG OUTPUT

function is displayed,

then press the CHANGE key.

(c) Press

the

▼ arrow key until OFF is

displayed, then press the ENTER key.

2. Start the unit in the Manual Mode at a valve

position between 25% and 30%.

3. The unit should shut down and execute an

IGNITION RETRY

cycle by performing the

following steps:

(a) The unit will execute a 30 second re-

ignition delay and display WAIT RETRY
PAUSE.

(b) The unit will then execute a standard

ignition sequence and display WAIT
IGNITION RETRY

.

4. The unit should perform two IGNITION

RETRY

cycles and then shut down on the

third successive ignition attempt. The unit
will display AIRFLOW FAULT DURING
PURGE.

6-4