beautypg.com

Benchmark 1.5ln low nox boiler, Gf-120 – AERCO BMK 1.5 LN October 2012 User Manual

Page 86

background image



CHAPTER 7

MAINTENANCE

Page 86 of 166 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 PR1:10/18/12

Benchmark 1.5LN Low NOx Boiler

Installation, Operation and Maintenance Manual

GF-120

OMM-0041 0E

Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power

1.

from the unit and turn off the gas supply.

Remove the side and top panels from the unit.

2.

Disconnect the lead wire from the flame detector installed on the burner plate. See

3.

Figure 7-4.

BLOWER

PROOF

SWITCH

BURNER

PLATE

BLOWER

IGNITER-

INJECTOR

HOSE

CLAMP

FLAME

DETECTOR

STAGED

IGNITION

ASSEMBLY

3/8-16

HEX NUTS

(8)

1/2" BOLTS

& NUTS (4)

AIR/FUEL

VALVE

BLOCKED
INLET
SWITCH

10-32 x 1 /2" LG

GROUNDING

SCREW

Figure 7-4: Burner Assembly Mounting Details

Remove the two (2) screws securing the flame detector to the plate. The flame detector

4.

is secured to the burner plate with one (1) #10-32 screw and one (1) #8-32 screw.

Remove the flame detector and gasket from the burner plate.

5.

Disconnect the cable from the igniter-injector.

6.

Using a 7/16” open-end wrench, disconnect the compression nut securing the gas

7.

injector tube of the igniter-injector to the elbow of the staged ignition assembly (see
Figure 7-2). Disconnect the staged ignition assembly from the igniter-injector.

Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end

8.

wrench.

Disconnect the unit wiring harness connectors from the air/fuel valve and blower motor.

9.

Disconnect the wire leads connected to the blower proof switch and blocked inlet switch

10.

(Figures 7-4 & 7-5).

Remove the 10-32 x 1/2" long. grounding screw from the burner plate (Figures 7-4 and

11.

7-5).

Disconnect the gas train from the air/fuel valve by removing the four (4) 1/2” bolts and

12.

nuts (Figure 7-4).