CHAPTER 4
INITIAL START-UP

Page 48 of 166 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 PR1:10/18/12

Benchmark 1.5LN Low NOx Boiler

Installation, Operation and Maintenance Manual

GF-120

OMM-0041 0E

4.2.1

Tools & Instrumentation

The following tools and instrumentation are necessary to perform combustion calibration of the
unit:

• Digital Combustion Analyzer: Oxygen accuracy to ± 0.4%; Carbon Monoxide (CO) and

Nitrogen Oxide (NOx) resolution to 1PPM.

• 16 inch W.C. manometer or equivalent gauge and plastic tubing.
• 1/4" NPT-to-barbed fittings for use with gas supply manometer or gauge.
• Small and large flat blade screwdrivers.
• Tube of silicone adhesive

4.2.2

Installing Gas Supply Manometer

The gas supply manometer (or gauge) is used to calibrate the gas pressure to be monitored on
the downstream side of the SSOV during the Combustion Calibration procedures described in
paragraph 4.4.

The gas supply manometer is installed at the downstream location on the 1/4” NPT port shown
in Figure 4-1. Note that a 1/4” plug must be removed from the port in order to install the
manometer.

Figure 4-1: Combustion Calibration & RSI Manometer Installation Locations

TO

AIR/FUEL

VALVE

GAS INLET

SSO

RSI

SOLENOID

VALVE

RSI BLEED-
OFF VALVE

1/4” NPT PLUG

(INSTALL

MONOMETER HERE

FOR

RSI PRESSURE

TEST/CALIBRATION)

MANUAL SHUT-
OFF VALVE

RSI

PRESSURE

REGULATOR

RSI GAS

VALVE

1/4” NPT PLUG

(INSTALL

MONOMETER HERE

FOR

COMBUSTION

CALIBRATION)