Chapter 7. maintenance, 1 maintenance schedule, Chapter 7 – AERCO BMK 1.5 LN October 2012 User Manual
Page 79: Maintenance, Gf-120, Benchmark 1.5ln low nox boiler

CHAPTER 7
MAINTENANCE
PR1: 10/18//12 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 Page 79 of 166
GF-120
OMM-0041 0E
Benchmark 1.5LN Low NOx Boiler
Installation, Operation and Maintenance Manual
CHAPTER 7. MAINTENANCE
7.1 MAINTENANCE SCHEDULE
The unit requires regular routine maintenance to keep up efficiency and reliability. For best
operation and life of the unit, the following routine maintenance procedures should be performed
in the time periods specified in Table 7-1. See Appendix I for a complete CSD-1 inspection
check list.
In order to perform the maintenance tasks specified in Table 7-1, the following maintenance kits
are available through your local AERCO Sales Representative:
• Annual Maintenance Kit, Part No. 58025-01
• 24-Month Waterside/Fireside Inspection Kit, Part No. 58025-05 (See NOTE below)
NOTE
The 24-Month Waterside/Fireside Inspection Kit also includes the items
contained in the Annual Maintenance Kit. Therefore, only Kit Part No.
58025-05 is required when performing the waterside/fireside inspections.
Appendix K contains recommended spare parts lists for maintenance of the boiler.
WARNING
TO AVOID PERSONAL INJURY, PRIOR TO SERVICING ENSURE THAT
THE FOLLOWING GUIDELINES ARE STRICTLY OBSERVED:
• DISCONNECT THE AC SUPPLY BY TURNING OFF THE SERVICE
SWITCH AND AC SUPPLY CIRCUIT BREAKER.
• SHUT OFF THE GAS SUPPLY AT THE MANUAL SHUT-OFF VALVE
PROVIDED WITH THE UNIT
• ALLOW THE UNIT TO COOL TO A SAFE WATER TEMPERATURE
TO PREVENT BURNING OR SCALDING
Table 7-1: Maintenance Schedule
Paragraph
Item
6 Mos.
12 Mos.
24 Mos.
Labor
Time
7.2
Igniter-Injector (58023)
*Inspect
Inspect
Replace
15 mins.
7.3
Flame Detector (24356-1)
*Inspect
Inspect
Replace
15 mins.
7.4
Combustion Calibration &
RSI Regulator Adjustment
*Check
Check
1 hr.
7.5
Testing of Safety Devices
See CSD-1
Chart in
Appendix I
20 mins.
7.6
Burner
Inspect
2 hrs.
7.7
Condensate Drain Trap
*Inspect
Inspect &
Clean
30 mins.
*Only performed after initial 6 month period after initial startup.