Appendix e: boiler default settings, Benchmark 2.0ln low nox boiler, Gf-120 – AERCO BMK 1.5 LN October 2012 User Manual

Page 126

background image


APPENDIX E

Benchmark 2.0LN Low NOx Boiler

GF-120

BOILER DEFAULTS

Installation, Operation and Maintenance Manual

OMM-0041_0E

Page 126 of 166 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 PR1:10/18/12

APPENDIX E: BOILER DEFAULT SETTINGS

Table E-1: Boiler Default Settings

MENU & OPTION

FACTORY DEFAULT

Setup Menu

Password

0

Language

English

Unit of Temp

Fahrenheit (ºF)

Comm Address

0

Baud Rate

9600

Configuration Menu

Internal Setpt

130°F

Unit Type

BMK Boiler LN

Unit Size

1500 MBH

Fuel Type

Natural Gas

Boiler Mode

Constant Setpoint

Remote Signal
(If Mode = Remote Setpoint, Direct Drive or Combination)

4 – 20 mA / 1-5V

Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)

70°F

Reset Ratio
(If Boiler Mode = Outdoor Reset)

1.2

Outdoor Sensor

Disabled

System Start Tmp
(If Outdoor Sensor = Enabled)

60°F

Setpt Lo Limit

60°F

Setpt Hi Limit

195°F

Temp Hi Limit

195°F

Max Valve Position

100%

Pump Delay Timer

0 min