beautypg.com

Circuit diagram, Input circuit, No-voltage input (when npn output is selected) – KEYENCE IV Series User Manual

Page 7: Voltage input (when pnp output is selected), Output circuit, When npn output is selected, When pnp output is selected

background image

7

IV Series (Sensor) - IM_E

Circuit Diagram

Input circuit

z

„

No-voltage input (When NPN output is selected)

When NPN is selected in I/O format, the circuit becomes

no-voltage input circuit. External power supply is not

necessary.

y

ON voltage

: 2 V or lower

y

OFF current

: 0.1 mA or lower

y

ON current

: 2 mA (short circuit)

+3.3V

DC24V

IN1 - IN6

0V

Brown

*

Blue

* Pink (IN1 : External trigger) / Yellow (IN2) / Light Blue (IN3) /

Purple (IN4) / Green (IN5) / Red (IN6)

Use by assigning the optional functions to IN2 to 6

Main circuit

z

„

Voltage input (When PNP output is selected)

When PNP is selected in I/O format, the circuit becomes

voltage input circuit.

y

Input maximum rating : 26.4 V

y

ON voltage

: 15 V or higher

y

ON current

: 2 mA (for 24V)

y

OFF current

: 0.2 mA or lower

DC24V

IN1 - IN6

0V

Brown

*

Blue

* Pink (IN1 : External trigger) / Yellow (IN2) / Light Blue (IN3) /

Purple (IN4) / Green (IN5) / Red (IN6)

Use by assigning the optional functions to IN2 to 6

Main circuit

Output circuit

z

„

When NPN output is selected

When NPN is selected in I/O format, the circuit becomes

open collector NPN output circuit.

y

Maximum rating

: 26.4 V, 50 mA

y

Remaining voltage : 1.5 V or lower

DC24V

OUT1 - OUT4

0V

Brown

*

Blue

* Black (OUT1) / White (OUT2) / Gray (OUT3) / Orange (OUT4)

Use by assigning the optional functions to OUT1 to OUT4

Main circuit

Overcurrent

protection circuit

Load

z

„

When PNP output is selected

When PNP is selected in I/O format, the circuit becomes

open collector PNP output circuit.

y

Maximum rating

: 26.4 V, 50 mA

y

Remaining voltage : 2 V or lower

DC24V

OUT1 - OUT4

0V

*

Blue

* Black (OUT1) / White (OUT2) / Gray (OUT3) / Orange (OUT4)

Use by assigning the optional functions to OUT1 to OUT4

Main circuit

Overcurrent

protection circuit

Load

Brown