Command parameter list for fd-mh series, Command parameter list for fd-mh series -26, 4 command parameter list – KEYENCE DL-CL1 User Manual
Page 54: Co mm u ni c a ting w ith t he fd -m h s er ie s

3-4 Command Parameter List
3-26
- CC-Link Compatible Network Unit DL-CL1 User’s Manual (FD-MH) -
Co
mm
u
ni
c
a
ting
w
ith t
he FD
-M
H
s
er
ie
s
3
The following tables provide command parameters for the FD-MH series. The two
types of parameters are: motion command parameters and setting/status command
parameters.
Motion command parameters
For the communication methods using motion command parameters, see
a Motion Command to a Sensor Amplifier" (page 3-20).
Attribute R: Read; C: Motion command
nn: ID number of sensor amplifier. Example: For nn05h and ID13, then 0D05h.
Setting/status command parameters
For the communication methods using setting/status parameters, see
Writing Settings or Status of a Sensor Amplifier" (page 3-21).
Attribute R: Read; W: Write; R/W: Read/Write
nn: ID number of sensor amplifier. Example: For nn41h and ID13, then 0D41h.
The data type is DINT (32-bit singed integer).
Command Parameter List for FD-MH Series
Data
category
(HEX)
Data
number
(HEX)
Name
Description
Attribute
00
nn00
Group-0 entry count
The default vaule is 5.
R
nn01
System reserved
nn02
Integrated fl ow quantity reset
request
Resets integrated fl ow quantity.
C
nn03
Reset request during hold
(instantaneous fl ow rate)
Resets instantaneous fl ow hold value.
C
nn04
Reset request during hold
(temperature display)
Resets temperature hold value.
C
nn05
Initial reset request (ALL)
Resets all settings of the sensor amplifi er to
the factory default settings.
C
Data
category
(HEX)
Data
number
(HEX)
Name
Description
Attribute
Sensor head
Default
value
Parameter range
00
nn20
Group-1 entry
count
R
-
22
nn21
Sensor amplifier
error state
*1
R
-
-
Bit 0: Head error (ErS)
Bit 1: Head connection error (ErH)
Bit 2: Overcurrent error (ErC)
Bit 3: EEPROM error (ErE)
Bit 4: Always 0
Bit 5: Always 0
Bit 6: Backflow error (rEv)
Bit 7: Always 0
Bit 8: Temperature lower limit error
Bit 8: Temperature upper limit error
Bit 10: Temperature sensor connection
error (Err tEMP)
Bits 11 to 15: Always 0
nn22
System reserved
nn23