Set point setup procedures, About set points, Three general rules for set points – Hardy WS100 Configuration Software User Manual
Page 35: Set point setup procedures -8, Fig. 5-6 setpoint screen -8
HI WS100 CONFIGURATION SOFTWARE
5-8
the motion value entered, the light next to
Motion Tolerance will turn to red. When
the scale motion is within the tolerance the
light turns green.
Step 10.
Click on the Save button to save the new
parameters.
Set Point Setup
Procedures
About Set Points
The set point value is the target weight or level. It may
be set in net, gross or Rate of Change (ROC). When
the set point is reached a relay is energized or de-ener-
gized depending what you want the relays to do. The
HI 1746-WS has two output relays which can be setup
in HI WS100 Configuration Software.
Step 1.
Click on the Setpoint Tab. The Setpoint
page appears. (See Fig. 5-6)
FIG. 5-6 SETPOINT SCREEN
Three General
Rules for Set
Points
1.
Set points activate at the set point plus the preact.
2.
Set points deactivate at the set point plus the
deadband.