Carrier 19XR,XRV Hermetic Centrifugal Liquid Chillers User Manual
Page 134

CL-10
19XR, XRV PIC II RAMP_DEM TABLE CONFIGURATION SHEET
19XR, XRV PIC II TEMP_CTL TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Pulldown Ramp Type:
Select: Temp=0, Load=1
0/1
1
Demand Limit + kW Ramp
Demand Limit Source
Select: Amps=0, kW=1
0/1
0
Motor Load Ramp% Min
5 to 20
10
Demand Limit Prop Band
3 to 15
%
10
Demand Limit At 20 mA
40 to 100
%
40
20 mA Demand Limit Opt
0/1
DSABLE/ENABLE
DSABLE
Motor Rated Kilowatts
50 to 9999
kW
145
Demand Watts Interval
5 to 60
MIN
15
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Control Point
ECW Control Option
0/1
DSABLE/ENABLE
DSABLE
Temp Pulldown Deg/Min
2 to 10
ˆF
3
Temperature Reset
RESET TYPE 1
Degrees Reset At 20 mA
–30 to 30
ˆF
10
RESET TYPE 2
Remote Temp -> No Reset
–40 to 245
DEG F
85
Remote Temp -> Full Reset
–40 to 245
DEG F
65
Degrees Reset
–30 to 30
ˆF
10
RESET TYPE 3
CHW Delta T -> No Reset
0 to 15
ˆF
10
CHW Delta T -> Full Reset
0 to 15
ˆF
0
Degrees Reset
–30 to 30
ˆF
5
Select/Enable Reset Type
0 to 3
0