19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Auto Restart Option
0/1
DSABLE/ENABLE
DSABLE
Remote Contacts Option
0/1
DSABLE/ENABLE
DSABLE
Soft Stop Amps Threshold
40 to 100
%
100
Surge/Hot Gas Bypass
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
0/1
0
Min. Load Point (T1, P1)
Surge/HGBP Delta T1
0.5 to 20
ˆF
1.5
Surge/HGBP Delta P1
30 to 170
PSI
50
Full Load Point (T2, P2)
Surge/HGBP Delta T2
0.5 to 20
ˆF
10
Surge/HGBP Delta P2
50 to 170
PSI
85
Surge/HGBP Deadband
0.5 to 3
ˆF
1
Surge Protection
Surge Delta% Amps
5 to 20
%
10
Surge Time Period
7 to 10
MIN
8
Ice Build Control
Ice Build Option
0/1
DSABLE/ENABLE
DSABLE
Ice Build Termination
0=Temp, 1=Contacts, 2=Both
0 to 2
0
Ice Build Recycle
0/1
DSABLE/ENABLE
DSABLE
Refrigerant Leak Option
0/1
DSABLE/ENABLE
DSABLE
Refrigerant Leak Alarm mA
4 to 20
mA
20
Head Pressure Reference
Delta P at 0% (4 mA)
20 to 60
psi
25
Delta P at 100% (20 mA)
20 to 60
psi
35
Minimum Output
0 to 100
%
0