Carrier 19XR,XRV Hermetic Centrifugal Liquid Chillers User Manual
Page 127

CL-3
19XR, XRV PIC II SETPOINT TABLE CONFIGURATION SHEET
CVC/ICVC Software Version
Number:
CVC/ICVC
Controller
Identification:
BUS:
ADDRESS:
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Base Demand Limit
40 to 100
%
100
ECW Setpoint
10 to 120
DEG F
60.0
LCW Setpoint
15 to 120
DEG F
50.0
Ice Build Setpoint
15 to 60
DEG F
40.0
Tower Fan High Setpoint
55 to 105
DEG F
75