19XR, XRV PIC II SETUP1 TABLE CONFIGURATION SHEET
DESCRIPTION
RANGE
UNITS
DEFAULT
VALUE
Comp Motor Temp Override
150 to 200
DEG F
200
Cond Press Override
90 to 165
PSI
125
Comp Discharge Alert
125 to 200
DEG F
200
Comp Thrust Brg Alert
165 to 185
DEG F
175
Chilled Medium
0/1
WATER/BRINE
WATER
Chilled Water Deadband
.5 to 2.0
ˆF
1.0
Evap Refrig Trippoint
0.0 to 40.0
DEG F
33
Refrig Override Delta T
2.0 to 5.0
ˆF
3
Condenser Freeze Point
–20 to 35
DEG F
34
Evap Flow Delta P Cutout
0.5 to 50.0
PSI
5.0
Cond Flow Delta P Cutout
0.5 to 50.0
PSI
5.0
Water Flow Verify Time
0.5 to 5
MIN
5
Oil Press Verify Time
15 to 300
SEC
40
Recycle Control
Restart Delta T
2.0 to 10.0
DEG F
5
Shutdown Delta T
0.5 to 4.0
DEG F
1
SPARE ALERT/ALARM ENABLE
Disable=0, Lo=1/3, Hi=2/4
Spare Temp #1 Enable
0 to 4
0
Spare Temp #1 Limit
–40 to 245
DEG F
245
Spare Temp #2 Enable
0 to 4
0
Spare Temp #2 Limit
–40 to 245
DEG F
245