PNOZ s7.1

Operating Manual PNOZ s7.1
21865-EN-08

6

Expansion options

Please note the max. power consumption of the

contact expansion modules (see technical data

PNOZ s7.1).

: Contact expansion module PNOZ s7.1 with ter-

minator

: Contact expansion module PNOZ s7.2

: Expansion module PNOZ s7, s8, s9, s10, s11

as a terminator

: Base unit

: Contact expansion module PNOZ s7.1

: Contact expansion module PNOZ s7.2

: Contact expansion module PNOZ s7.1

: Contact expansion module PNOZ s7.2

: Contact expansion module PNOZ s7.2 with ter-

minator

Wiring

Please note:

}

Information given in the "Technical details" must be followed.

}

The output contacts 13-14, 23-24, 33-34 are safety contacts.

}

To prevent contact welding, a fuse should be connected before the output contacts (see

technical details).

}

Calculation of the max. cable length l

max

in the input circuit:

R

lmax

R

l

/ km

I

max

=

R

lmax

= max. overall cable resistance (see technical details)

R

l

/ km = cable resistance/km

}

Use copper wire that can withstand 60/75 °C.

}

Sufficient fuse protection must be provided on all output contacts with capacitive and in-

ductive loads.