Pilz PNOZ s3 C 24VDC 2 n/o User Manual

Page 14

background image

PNOZ s3

Operating Manual PNOZ s3
21395-EN-10

14

Times

750103

751103

Delay-on de-energisation

With E-STOP typ.

10 ms

10 ms

With E-STOP max.

20 ms

20 ms

With power failure typ.

40 ms

40 ms

With power failure max.

60 ms

60 ms

Recovery time at max. switching

frequency 1/s

After E-STOP

100 ms

100 ms

After power failure

100 ms

100 ms

Waiting period with a monitored re-

set

With rising edge

120 ms

120 ms

With falling edge

250 ms

250 ms

Min. start pulse duration with a

monitored reset

With rising edge

30 ms

30 ms

With falling edge

100 ms

100 ms

Supply interruption before de-ener-

gisation

20 ms

20 ms

Simultaneity, channel 1 and 2

Environmental data

750103

751103

Climatic suitability

EN 60068-2-78

EN 60068-2-78

Ambient temperature

Temperature range

-10 - 55 °C

-10 - 55 °C

Storage temperature

Temperature range

-40 - 85 °C

-40 - 85 °C

EMC

EN 60947-5-1, EN 61000-6-2, EN

61000-6-4

EN 60947-5-1, EN 61000-6-2, EN

61000-6-4

Vibration

In accordance with the standard

EN 60068-2-6

EN 60068-2-6

Frequency

10,0 - 55,0 Hz

10,0 - 55,0 Hz

Max. amplitude

0,35 mm

0,35 mm

Airgap creepage

In accordance with the standard

EN 60947-1

EN 60947-1

Overvoltage category

III / II

III / II

Pollution degree

2

2

Rated insulation voltage

250 V

250 V

Rated impulse withstand voltage

4,00 kV

4,00 kV

Protection type

Mounting (e.g. cabinet)

IP54

IP54

Housing

IP40

IP40

Terminals

IP20

IP20

This manual is related to the following products: