Faults - malfunctions – Pilz PNOZ s3 C 24VDC 2 n/o User Manual
Page 10
![background image](/manuals/647237/10/background.png)
PNOZ s3
Operating Manual PNOZ s3
21395-EN-10
10
In1
Fault
Diagnostics: Power-up blocked due to short-term interruption at S12; input cir-
cuits not operated simultaneously
}
Remedy: Open both input circuits, S12 and S22, simultaneously and then
close again.
In2
Fault
Diagnostics: Power-up blocked due to short-term interruption at S22; input cir-
cuits not operated simultaneously
}
Remedy: Open both input circuits, S12 and S22, simultaneously and then
close again.
Reset
Fault
Diagnostics: Position of rotary switch is not permitted or rotary switch was ad-
justed during operation.
}
Remedy: Switch supply voltage off and then on again.
Power, In1, In2, Out, Reset, Fault
Diagnostics: The operating mode selector switch "mode" is in its start position
(vertical position)
}
Remedy: Switch off the supply voltage and set the required operating mode
on operating mode selector switch "mode".
Faults - malfunctions
}
Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.