Operation

The unit is ready for operation when the Power LED is permanently lit.
LEDs indicate the status and errors during operation:

LED on

LED flashes

Information
Status indicators and error indicators may occur independently. In the case
of an error display, the "Fault" LED will light or flash (exception: "Supply
voltage too low"). An LED that is also flashing indicates the potential cause
of the error. An LED that is lit and is static indicates a normal operating sta-
tus. Several status indicators and error indicators may occur simultaneously.

Status indicators

Power, In1, In2

Input circuit is closed.

Out

Safety contacts are closed and semiconductor output Y32 carries a high signal.

Reset

24 V DC is present at S34.

Error indicators

Fault

Diagnostics: Plug terminator not connected

}

Remedy: Insert plug terminator, switch supply voltage off and then on

again.

Fault

Diagnostics: Internal error, unit defective

}

Remedy: Switch supply voltage off and then on again, change unit if neces-

sary.

Power

Diagnostics: Supply voltage too low

}

Remedy: Check the supply voltage.