Technical details – Pilz PNOZ s2 C 24VDC 3 n/o 1 n/c User Manual
Page 10

PNOZ s2
Operating Manual PNOZ s2
21394-EN-07
10
Example
}
Inductive load: 0,2 A
}
Utilisation category: AC15
}
Contact service life: 2,000,000 cycles
Provided the application requires fewer than 2,000,000 cycles, the PFH value (see techni-
cal details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With contac-
tors, use freewheel diodes for spark suppression.
Technical Details
General
750102
751102
Approvals
CCC, CE, GOST, KOSHA, TÜV,
cULus Listed
CCC, CE, GOST, KOSHA, TÜV,
cULus Listed
Electrical data
750102
751102
Supply voltage
Voltage
24 V
24 V
Type
DC
DC
Voltage tolerance
-15 %/+10 %
-15 %/+10 %
Output of external power supply
(DC)
2,0 W
2,0 W
Residual ripple DC
20 %
20 %
Continuous duty
100 %
100 %
Max. inrush current impulse
Reset circuit
0,50 A
0,50 A
Feedback loop
0,50 A
0,50 A
Max. overall cable resistance Rl-
max
Single-channel at UB DC
30 Ohm
30 Ohm
Voltage at
Input circuit DC
24,0 V
24,0 V
Reset circuit DC
24,0 V
24,0 V
Feedback loop DC
24,0 V
24,0 V
Current at
Input circuit DC
75,0 mA
75,0 mA
Reset circuit DC
7,0 mA
7,0 mA
Feedback loop
7,0 mA
7,0 mA
Number of output contacts
Instantaneous safety contacts
(N/O)
3
3
Auxiliary contacts (N/C)
1
1
Inputs
750102
751102
Number
1
1