beautypg.com

Pilz PNOZ s2 C 24VDC 3 n/o 1 n/c User Manual

Page 12

background image

PNOZ s2

Operating Manual PNOZ s2
21394-EN-07

12

Relay outputs

750102

751102

Contact material

AgCuNi + 0,2 µm Au

AgCuNi + 0,2 µm Au

Conventional thermal current

while loading several contacts

750102

751102

Ith per contact at UB DC

Conv. therm. current with 1 con-

tact

6,00 A

6,00 A

Conv. therm. current with 2 con-

tacts

6,00 A

6,00 A

Conv. therm. current with 3 con-

tacts

5,00 A

5,00 A

Times

750102

751102

Switch-on delay

With automatic reset typ.

75 ms

75 ms

With automatic reset max.

250 ms

250 ms

With automatic reset after power

on typ.

75 ms

75 ms

With automatic reset after power

on max.

250 ms

250 ms

With manual reset typ.

75 ms

75 ms

With manual reset max.

250 ms

250 ms

With monitored reset with rising

edge typ.

75 ms

75 ms

With monitored reset with rising

edge max.

250 ms

250 ms

With monitored reset with falling

edge typ.

55 ms

55 ms

With monitored reset with falling

edge max.

70 ms

70 ms

Delay-on de-energisation

With E-STOP typ.

50 ms

50 ms

With E-STOP max.

70 ms

70 ms

With power failure typ.

50 ms

50 ms

With power failure max.

70 ms

70 ms

Recovery time at max. switching

frequency 1/s

After E-STOP

100 ms

100 ms

After power failure

100 ms

100 ms

Waiting period with a monitored re-

set

With rising edge

100 ms

100 ms

With falling edge

110 ms

110 ms

Min. start pulse duration with a

monitored reset

With rising edge

100 ms

100 ms

With falling edge

100 ms

100 ms

Supply interruption before de-ener-

gisation

10 ms

10 ms

This manual is related to the following products: