Pilz PNOZ s2 C 24VDC 3 n/o 1 n/c User Manual
Page 12

PNOZ s2
Operating Manual PNOZ s2
21394-EN-07
12
Relay outputs
750102
751102
Contact material
AgCuNi + 0,2 µm Au
AgCuNi + 0,2 µm Au
Conventional thermal current
while loading several contacts
750102
751102
Ith per contact at UB DC
Conv. therm. current with 1 con-
tact
6,00 A
6,00 A
Conv. therm. current with 2 con-
tacts
6,00 A
6,00 A
Conv. therm. current with 3 con-
tacts
5,00 A
5,00 A
Times
750102
751102
Switch-on delay
With automatic reset typ.
75 ms
75 ms
With automatic reset max.
250 ms
250 ms
With automatic reset after power
on typ.
75 ms
75 ms
With automatic reset after power
on max.
250 ms
250 ms
With manual reset typ.
75 ms
75 ms
With manual reset max.
250 ms
250 ms
With monitored reset with rising
edge typ.
75 ms
75 ms
With monitored reset with rising
edge max.
250 ms
250 ms
With monitored reset with falling
edge typ.
55 ms
55 ms
With monitored reset with falling
edge max.
70 ms
70 ms
Delay-on de-energisation
With E-STOP typ.
50 ms
50 ms
With E-STOP max.
70 ms
70 ms
With power failure typ.
50 ms
50 ms
With power failure max.
70 ms
70 ms
Recovery time at max. switching
frequency 1/s
After E-STOP
100 ms
100 ms
After power failure
100 ms
100 ms
Waiting period with a monitored re-
set
With rising edge
100 ms
100 ms
With falling edge
110 ms
110 ms
Min. start pulse duration with a
monitored reset
With rising edge
100 ms
100 ms
With falling edge
100 ms
100 ms
Supply interruption before de-ener-
gisation
10 ms
10 ms