beautypg.com

Anode inspection and replacement – Bradford White EF-100T-399-3X User Manual

Page 74

background image

Anode inspection and replacement

Step 1.

Turn off water supply and drain water heater.

Step 2.

Disassemble water heater per “Disassembly Procedure for Access to Andoes & Flue Baffles”.

Step 3.

Locate and remove anode rods from heater (1-1/16 hex socket).

Step 4.

Visually inspect anode rod. Anode rod should show signs of depletion, this is normal. If

the depletion is ½ of the original diameter (approximately ¾" diameter), replacement is

recommended. If any of the steel core of the anode is exposed, replacement is

recommended.

Step 5.

Upon completion of inspection or subsequent replacement, apply thread sealing tape or other

thread compound to threads of anode and reinstall into heater. Restore water supply

and check for and repair any leaks found.

Step 6.

Reinstall collector cover per “Collector Cover Installation Procedure”.

Step 7.

Reinstall collector insulation and control panel, reconnect control panel wire harnesses.

Step 8.

Restore 120 volts to water heater and verify proper heater operation following the

instructions on the lighting instruction label or the lighting instruction located in the

installation and operating instruction manual.

Step 9.

Replace surround cover on top of water heater.

WARNING

Heater components and stored water may be HOT when performing the following steps in

this procedure. Take necessary precaution to prevent personal injury.

74

74

This manual is related to the following products: