Bradford White EF-100T-399-3X User Manual
Page 26
Accessing Service Mode on Control Display
For models with Honeywell Integrated Control
To Display Flame Sense Current of the Pilot Flame Sensor:
The pilot flame sense current is available only when the burners are in operation. Step 1: Make sure the status displays
“Heating” or draw enough hot water to start the burners. Step 2: Enter the “Service Mode” described previously. Step 3:
Press the “Select” button until a number value is displayed with “Flame Current” to the right of the number. The value
displayed is in microamps (µA).
SELECT
SET
Status Operational
Flame
Current
Heating
µA
To Display and Change Temperature Setpoint:
Step 1: In “Service Mode” press the “Select” button until “Setpoint” is shown in the water heater display
SELECT
SET
Status
°F
idle
setpoint
Operational
26