Inspect the area housing the combustion

system and control panel located at the

top of the heater.

Does the area show signs of corrosion

and/or exssesive heat?

Y

N

Call for

technical support

Remove combustion assembly

(see “Combustion System

Removal Procedure”)

Inspect combustion chamber

for blockage or debris

accumulation

N

Replace

exhaust pressure switch.

(see “Exhaust Pressure Switch

Replacement Procedure”)

Is exhaust venting

system blocked or

obstructed?

Clear obstruction.

Determine cause

and correct.

Y

Is vent system total

length compliant with

vent tables in the

instruction manual?

Reconfigure vent

system to be

compliant with

vent tables (see

“Specifications”).

Y

N

With monometer, take a

reading at the

exhaust

tube pressure tap location.

Is value negative (-)?

(see illustration below).

Check exhaust collector pressure at the exhaust

collector pressure tap location (see illustration below). Is

there positive pressure equal to or greater than

pressure switch settings below?

EXHAUST PRESSURE SWITCH SETTINGS

EF(60,100)T199

+2.58" W.C.

EF100T150

+1.50" W.C.

(see note 1)

EF60T150,EF100T250

+1.22" W.C.

EF60T125

+2.08" W.C.

EF100T300

+0.55" W.C.

(see note 2)

Note 1: +5.6" W.C. on serials prior to AH5039107

Note 2: +0.8" W.C. on serials prior to AK5288269

Y

N

Y

Y

N

N

Clear obstruction.

Determine cause

and correct.

Check Collector Pressure

Call for

technical support

Exhaust Pressure Switch Testing and Replacement

For serial numbers prior to “CF”

Exhaust Tube

pressure tap location

Exhaust collector

pressure tap location

Exhaust tube

at bottom of water

heater

55