beautypg.com

Warning – Bradford White EF-100T-399-3X User Manual

Page 69

background image

Is there continuity

through the normally

closed intake pressure

switch?

(see photo at right)

Y

Replace

intake pressure switch.

(see “Intake Pressure Switch

Replacement Procedure”)

Switch OK.

Does Blower Energize?

Does purge LED

illuminate on the ignition

module?

Remove hose from intake

pressure switch and

Restart heater.

Does purge LED illuminate?

N

Y

With manometer, take a

reading from the inlet tube

pressure tap. Is reading

negative (-)1.2" W.C.

or more?

(see illustration below)

N

See “Vent Safety Switch Testing

and Replacement”

or

Exhaust Pressure Switch Tesinting

and Replacement”

or

“Blower Testing and Replacement”

Y

N

Y

N

N

Y

Is intake vent system

obstructed?

Y

N

Call for technical support.

Clear obstruction.

See “Exhaust Pressure Switch Testing

and Replacement”)

or

“Blower Testing and Replacement”

Used on EF water heaters prior to “CF” serial number.

Is there continuity

through the normally

closed intake pressure

switch?

(see photo above)

Y

Isolate (disconnect) heater from

intake vent system and

Restart heater.

Does purge LED illuminate?

N

Y

N

Disconnect red wire leads from

pressure switch and check

continuity through switch.

WARNING

120 volt potential exposure. Use caution

making voltage checks to avoid personal injury.

Notice:

The intake pressure switch is not used

on serial number “CF” and later.

Inlet Tube

pressure tap

69

69

This manual is related to the following products: