I

nstallation of Recessed Back

Box in New Construction

1.Mounting Back Box (See Figure 1).

a. Place the back box between two 16" (406 mm) center-to-center wall

studs at the desired mounting height but no closer than 8" (203 mm)

to adjacent wall or floor.

Note: If wall studs are spaced greater than 16” on center, additional

framing supports may be necessary.

b. Align back box such that the bottom and sides will be flush with

finished wall surface (top flange of back box should protrude approxi-

mately 1/2" (12.7 mm) from finished wall surface).

c. Secure the back box in position with wood screws or nails as shown

in Figure 1.

2.Power Supply Wiring (See Figure 1)

Note: Wire compartment volume - 119in

3

(1950cm

3

).

a. Run a power supply cable into the knockout area in the upper right

hand corner of the back box. All wiring must be in accordance with

National and Local Electrical Codes. Refer to Table 1 for correct

wire size.

b. Remove disconnect switch bracket by loosening two screws on the

right side.

c. Install a cable clamp in the “knockout” in the top of the back box.

d. Insert power supply cable through cable clamp, allowing at least 6"

(152mm) of leads to extend inside the back box. Connect the blue

lead wires of disconnect switch to the supply wire leads using wire

connectors (see wiring diagram, pg. 4).

e. Ground the back box using the green screw located in the inside top

of the back box.

f. Secure disconnect switch bracket in place by tightening screws.

Installation of Recessed Back Box

in Existing Construction

1. Provide a wall opening 14-1/2" (362mm) wide by 18-1/2" (470mm) high

at the desired mounting height, but no closer than 8" (203mm) from floor.

(See Figure 2.)

Note: Locate so at least one side of opening is at wall stud.

2. Power Supply Wiring
Note: Wiring Compartment Volume - 119in

3

(1950cm

3

).

a. Run a power supply cable into the area above the top of the wall open-

ing. All wiring must be in accordance with National and Local electrical

codes. Refer to Table 1 for correct wire size.

b. Remove disconnect switch bracket by loosening the two screws on the

right side.

c. Install a cable clamp in the “knockout” in the top of back box.
d. Insert power supply cable through cable clamp, allowing approximate-

ly 6" (152mm) of cable length to remain inside the back box to facili-

tate connections.

3. Mounting Back Box

a. Place the back box into wall opening flush with finished wall surface on

bottom and sides of box. (Top flange of back box should protrude

approximately 1/2" or 12.7mm from finished wall surface).

b. Secure the back box in place with wood screws or nails.

4. Wiring Disconnect Switch

a. Connect the power supply wires to the blue wires of the disconnect switch

using wire connectors (see wiring diagram,pg. 4.)

b. Ground the back box using the green ground screw located in the

inside top of the back box.

c. Secure disconnect switch bracket in place by tightening screws.

CAUTION

FOR SAFE OPERATION AND REDUCED RISK OF FIRE, INJURY OR

HEATER DAMAGE, OBSERVE THE FOLLOWING:
1. Do NOT use a remote thermostat with this heater. Built in thermostat

cycles the heating element only. Fan delay control automatically turns

fan ON and OFF, and provides a fan delay OFF feature to remove

residual heat after thermostat has turned heating elements off. Wiring

of heater in any manner which defeats the fan delay OFF feature can

result in overheating and permanent damage to heater, and will void

the warranty.

2. For wall mounting only with air discharge downward. Do NOT install

in floor, ceiling, upside down (air discharge upward), or sideways.

3. Do NOT operate heater without grille installed.
4. Maintain the following clearances:

• Bottom of heater to floor – 8” (203mm)
• Sides of heater to adjacent wall – 8” (203mm)
• Top of heater to ceiling – 36” (915mm)

5. This heater is hot when in use. Do NOT install heater behind door,

behind towel rack, inside closet, where drapery could touch heater or

be damaged by heat, or where airflow to heater may be obstructed.

Keep electrical cords, bedding, furniture, and other items away from

heater.

6. Heater must be cleaned periodically (at least annually) to assure

proper performance and prevent overheating. See section on

cleaning and maintenance.

Fig. 1: Locating Back Box in New Construction

Fig. 2: Locating Back

Box in Existing Construction

!

8” (203mm) MIN

!

Back Box

Back Box

Table 1

Min.

Supply

Catalog

Wire

Number

Volts

Phase

Watts

Amps

Gauge

WH3150

120

1

1500

12.5

12

WH3180

120

1

1800

15.0

12

WH4404*

240/208

1

4000/3000 16.7/14.5

10

2000/1500 8.3/7.2

12

WH4407*

277/240

1

4000/3000 14.5/12.5

12

2000/1500 7.2/6.3

12

WH4307*

277

1

3000/1500 10.8/5.4

12

WH4408*

208

1

4000/2000 19.2/9.6

10

WH44083

208

3

4000

11.1

14

WH44043

240

3

4000

9.7

14

WH4303

347

1

3000

8.6

14

WH4306

600

3

3000

3

14

WH4508

208

1

4800

23.1

10

WH4504

208/240

1

3600/4800 17.3/20.0

10

WH4507

240/277

1

3600/4800 15.0/17.3

10

WH45083

208

3

4800

13.3

12

WH45043

240

3

4800

11.6

14

WH4503

347

1

4800

13.8

12

WH4506

600

1

4800

8

14

*NOTE: Factory wired for higher wattage, field convertible to half wattage.