Carrier 62E User Manual
Page 4
4
Table 1B — Physical Data — English
LEGEND
UNIT 62E
BA/7A
BC/7C
CC/2C
CD/2D
CG/2G
DD/3D
DG/3G
NOMINAL CAPACITY (cfm)
350
500
1000
900
1100
1300
1600
CAPACITY RANGE (cfm)
200-800
200-900
500-1150
400-1100
500-1400
600-1600
800-2000
MAXIMUM SHIPPING WEIGHT (lb)
331
336
488
502
502
627
627
MAXIMUM OPERATING WEIGHT (lb)
281
286
438
452
452
577
577
UNIT DIMENSIONS (in.)
Length (includes hoods)
44.2/48.9
61.8/57.5
67.6/57.3
Width
31.1/36.4
38.6/43.9
44.4/49.7
Height
34.6/31.2
42.1/38.7
41.9/44.5
ROTARY ENERGY EXCHANGER
Type
Monolithic
Segmented
Size (Diam x Depth) (in.)
19 x 1.0
19 x 2.0
25 x 2.0
25 x 3.0
30 x 3.0
Nominal Drive Motor Hp
0.09
0.09
0.09
0.09
0.09
SUPPLY/EXHAUST FANS
Type
Centrifugal DWDI
Backward Inclined, Single Width Single Inlet
Drive Type
Direct
EC Motor with Integral Frequency Drive
Fan Option Code
(see fan option table)
A
A, B
C
C
FILTERS
Type
2 in. Pleated
Exhaust Air – Qty...Size (L x W x D) (in.)
1...12 x 24 x 2
1…14 x 25 x 2
2…16 x 25 x 2
Outside Air – Qty...Size (L x W x D) (in.)
1...12 x 24 x 2
1…14 x 25 x 2
2…16 x 25 x 2
UNIT 62E
EB/4B
ED/4D
EF/4F
EG/4G
HB/5B
HD/5D
HF/5F
HG/5G
KD/6D
KG/6G
NOMINAL CAPACITY (cfm)
1,400
2,200
2,200
2,600
3,000
4,600
4,600
5,500
4,500
7,800
CAPACITY RANGE (cfm)
800-
1,800
1,100-
2,600
1,300-
2,700
1,300-
3,500
1,400-
3,600
2,200-
5,600
2,200-
5,400
3,000-
7,400
2,500-
5,500
4,000-
10,500
MAXIMUM SHIPPING
WEIGHT (lb)
1,120
1,158
1,120
1,158
1,739
1,771
1,739
1,771
2,550
2,550
MAXIMUM OPERATING
WEIGHT (lb)
1,070
1,108
1,070
1,108
1,689
1,721
1,689
1,721
2,300
2,300
UNIT DIMENSIONS (in.)
Length (includes hoods)
85.5/70.8
103.9/80.1
114.5/86.1
Width
54.6/59.9
67.0/72.3
77.6/82.9
Height
50.5/54.7
55.9/67.1
61.9/77.7
ROTARY ENERGY
EXCHANGER
Type
Segmented
Size (Diam x Depth) (in.)
36 x 1.5
36 x 3.0
36 x 1.5
36 x 3.0
52 x 1.5
52 x 3.0
52 x 1.5
52 x 3.0
64 x 3.0
Nominal Drive Motor Hp
1/6
1/6
1/6
1/6
1/6
1/6
1/4
SUPPLY/EXHAUST FANS
Type
Backward Inclined, Single Width Single Inlet
Drive Type
EC Motor with Integral Frequency Drive
Fan Option Code
(see fan option table)
C, E
E, F
E, F, L
E, F, L, M
F, L, M
FILTERS
Type
2 in. Pleated
Exhaust Air – Qty...Size
(L x W x D) (in.)
2…20 x 25 x 2
3…20 x 25 x 2
6…16 x 24 x 2
Outside Air – Qty...Size
(L x W x D) (in.)
2…20 x 25 x 2
3…20 x 25 x 2
6…16 x 24 x 2
DWDI — Double Width, Double Inlet
EC