Carrier 62E User Manual
Page 13

13
CLEARANCE
"A"
CLEARANCE
"B"
CLEARANCE
36.000
DUCT CONNECTION
SPACE IF NO HOODS
"C"
SEE NOTE 3
FIELD TERMINAL STRIP
ACCESS
OUTSIDE AIR
HOOD
EXHAUST
HOOD
WHEEL AND FILTER
ACCESS
ROOF CURB
ROOF CURB
DISCONNECT
LOCATION
OUTSIDE AIR
HOOD
EXHAUST
HOOD
DUCT CONNECTION
SPACE
"G"
"F"
"E"
DUCT O.D.
"D"
"H"
"I"
"J"
DUCT O.D.
"D"
DUCT I.D.
"D" - 2.000
DUCT I.D.
"K"
DUCT I.D.
"K"
S/A
R/A
ONLY DUCT SLEEVE AND
ERV AIR DIVIDER SHOWING
62E UNIT TYPE
DIMENSIONS (in.)
A
B
C
D
E
F
G
H
I
J
K
7
36.000
36.000
1.869
28.995
31.734
36.375
32.176
31.186
11.984
36.905
12.813
2
18.000
36.000
1.179
36.495
39.171
43.875
39.663
38.673
16.215
41.239
16.497
3
18.000
40.000
3.795
42.295
44.847
49.675
45.463
44.473
16.215
41.099
19.272
4
18.000
50.000
4.238
52.495
55.066
59.875
55.673
54.673
21.132
49.631
23.997
5
24.000
64.000
4.516
64.915
67.486
72.295
68.093
67.093
27.131
53.013
30.207
6
18.000
75.000
9.542
75.495
78.066
82.875
78.673
77.673
27.131
58.963
35.247
Fig. 10 — 62E2-62E7 Unit Cabinet Dimensions
NOTES:
1. Clearance above cabinet is 24 in. (610 mm).
2. Dimensions are in inches.
3. Size the roof curb to allow for a clearance of 10-in. (254 mm) (minimum) between
the bottom of the exhaust hood and the top of the insulated roof material.
62E UNIT TYPE
DIMENSIONS (mm)
A
B
C
D
E
F
G
H
I
J
K
7
914
914
47
736
806
924
817
792
304
937
325
2
457
914
30
927
995
1114
1007
982
412
1047
419
3
457
1016
96
1074
1139
1262
1155
1130
412
1044
490
4
457
1270
108
1333
1399
1521
1414
1389
537
1261
610
5
610
1626
115
1649
1714
1836
1730
1704
689
1347
767
6
457
1905
242
1918
1983
2105
1998
1973
689
1498
895