beautypg.com

Carrier 62E User Manual

Page 13

background image

13

CLEARANCE

"A"

CLEARANCE

"B"

CLEARANCE

36.000

DUCT CONNECTION

SPACE IF NO HOODS

"C"

SEE NOTE 3

FIELD TERMINAL STRIP
ACCESS

OUTSIDE AIR
HOOD

EXHAUST
HOOD

WHEEL AND FILTER

ACCESS

ROOF CURB

ROOF CURB

DISCONNECT
LOCATION

OUTSIDE AIR
HOOD

EXHAUST
HOOD

DUCT CONNECTION

SPACE

"G"

"F"

"E"

DUCT O.D.

"D"

"H"

"I"

"J"

DUCT O.D.

"D"

DUCT I.D.

"D" - 2.000

DUCT I.D.

"K"

DUCT I.D.

"K"

S/A

R/A

ONLY DUCT SLEEVE AND

ERV AIR DIVIDER SHOWING

62E UNIT TYPE

DIMENSIONS (in.)

A

B

C

D

E

F

G

H

I

J

K

7

36.000

36.000

1.869

28.995

31.734

36.375

32.176

31.186

11.984

36.905

12.813

2

18.000

36.000

1.179

36.495

39.171

43.875

39.663

38.673

16.215

41.239

16.497

3

18.000

40.000

3.795

42.295

44.847

49.675

45.463

44.473

16.215

41.099

19.272

4

18.000

50.000

4.238

52.495

55.066

59.875

55.673

54.673

21.132

49.631

23.997

5

24.000

64.000

4.516

64.915

67.486

72.295

68.093

67.093

27.131

53.013

30.207

6

18.000

75.000

9.542

75.495

78.066

82.875

78.673

77.673

27.131

58.963

35.247

Fig. 10 — 62E2-62E7 Unit Cabinet Dimensions

NOTES:

1. Clearance above cabinet is 24 in. (610 mm).
2. Dimensions are in inches.
3. Size the roof curb to allow for a clearance of 10-in. (254 mm) (minimum) between

the bottom of the exhaust hood and the top of the insulated roof material.

62E UNIT TYPE

DIMENSIONS (mm)

A

B

C

D

E

F

G

H

I

J

K

7

914

914

47

736

806

924

817

792

304

937

325

2

457

914

30

927

995

1114

1007

982

412

1047

419

3

457

1016

96

1074

1139

1262

1155

1130

412

1044

490

4

457

1270

108

1333

1399

1521

1414

1389

537

1261

610

5

610

1626

115

1649

1714

1836

1730

1704

689

1347

767

6

457

1905

242

1918

1983

2105

1998

1973

689

1498

895