Step 7 — Make Electrical Connections

POWER SUPPLY — The electrical characteristics of the

available power supply must agree with the unit nameplate

rating. Supply voltage must be within the limits shown. See Ta-

bles 3-5 for electrical and configuration data.
ELECTRICAL CONNECTIONS — The ERV unit must

have its own electrical disconnect box. If the disconnect option

has not been ordered from the factory, it must be field supplied

and installed per local codes. See Tables 3-5.

If the ERV unit has an electric pre-heater factory installed, it

will be wired through the ERV unit disconnect.
Low Voltage Wiring — Wire low voltage per Fig. 14. The

field connection terminal strip is located behind the panel that

is adjacent to the control box. The correct panel is marked with

a green label stating “Attention: For field control of ERV, re-

move this panel to gain access to ERV field control terminal

strip.” The wires connecting to the field terminal strip can be

routed through the nearest

3

/

4

-in. hole and through conduit to

the RTU, or they can be routed down the sidewall of the cabi-

net using the wire pull provided and routed through the combi-

nation curb to the RTU.

If the ERV unit is mated to a RTU, terminals C and G on the

field control terminal strip of the ERV unit are connected to the

corresponding terminals on the RTU cabinet. Verify the jumper

is removed from the “ERV R” and “G” terminals; not doing so

may damage RTU control equipment.

When the ERV is to be run as a stand-alone configuration,

verify that a jumper is shorting the “ERV R” and “G” terminals

on the ERV field control terminal strip. This will enable the

ERV to turn on and run.

If the HVAC unit has an integrated economizer or power ex-

haust, it is sometimes necessary to provide an interface be-

tween the HVAC unit and the ERV controls to ensure proper

operation of the ERV’s supply/exhaust fan and energy recovery

wheel motors. The 62E has discrete inputs for this purpose and

damper end switches or relays may be used to coordinate the

economizer and power exhaust operation with the ERV.

When an ERV is mated to an electro-mechanical rooftop

unit with an economizer and a power exhaust, terminals C and

G on the ERV field control terminal strip are still connected to

the corresponding terminals on the rooftop unit cabinet (jumper

across R and G needs to be removed). However, in addition,

field supplied and installed end switches are required to coordi-

nate operation with the unit. For unit economizer operation, it

is necessary to install an Normally Open end switch (field pro-

vided) on the economizer actuator and connect to terminals 5

and 6 (ERV Shutdown) on the ERV terminal strip. This will

cause the ERV to shut down during unit economizer operation.

For power exhaust, based on building pressure control, no ad-

ditional ERV wiring is required, however if the ERV is to pro-

vide power exhaust functionality then a field-installed Normal-

ly Closed end switch is required to be installed between termi-

nals 7 and 8 on the ERV terminal strip.
High Voltage Wiring — Connect high voltage wiring to the

disconnect, see Fig. 14. Route the power wires in water tight

conduit from the disconnect switch box to the ERV distribution

block. To gain access to high voltage block, remove panel

marked with label stating, “High voltage terminal block locat-

ed behind this panel.”

Table 3 —

ERV Wheel Motor and Control

Transformer Electrical Data

LEGEND

WARNING

Prior to performing service or maintenance operations on

the ERV unit, turn off and disconnect all power switches to

the unit. Be aware that there may be more than one discon-

nect switch. Electrical shock could cause serious personal

injury or death.

IMPORTANT: Only trained, qualified installers and ser-

vice technicians should install, wire, start-up and service

equipment.

CAUTION

When routing wires in the ERV always keep them away

from moving parts and sharp metal edges. Follow all local

and state codes when routing the ERV control wires.

Fig. 13 — Rigging and Handling

FORK POCKETS

EYE HOOK
(HIDDEN)

EYE HOOK

EYE HOOKS

a62-380

UNIT

UNIT

V-Ph

ERV WHEEL MOTOR

CONTROL

TRANSFORMER

V-Ph

W

FLA

V

FLA

62EB,E7

115-1

115-1

80.5

0.70

75

0.65

230-1

230-1

69.0

0.30

75

0.33

230-3

230-1

69.0

0.30

75

0.33

400-3

230-1

69.0

0.15

75

0.16

460-3

230-1

69.0

0.15

75

0.16

575-3

230-1

69.0

0.12

75

0.13

62EC,E2

230-1

230-1

69.0

0.30

75

0.33

230-3

230-1

69.0

0.30

75

0.33

400-3

230-1

69.0

0.15

75

0.16

460-3

230-1

69.0

0.15

75

0.16

575-3

230-1

69.0

0.12

75

0.13

62ED,E3

230-3

230-1

69.0

0.30

75

0.33

400-3

230-1

69.0

0.15

75

0.16

460-3

230-1

69.0

0.15

75

0.16

575-3

230-1

69.0

0.12

75

0.13

62EE,E4

230-3

230-3

138.3

1.04

75

0.33

400-3

460-3

138.3

0.52

75

0.16

460-3

460-3

138.3

0.52

75

0.16

575-3

575-3

99.7

0.30

75

0.13

62EH,E5

230-3

230-3

99.7

0.75

75

0.33

400-3

460-3

101.0

0.38

75

0.16

460-3

460-3

101.0

0.38

75

0.16

575-3

575-3

99.7

0.30

75

0.13

62EK,EL,EM,

EN,EP,E6

230-3

230-3

332.4

2.50

75

0.33

400-3

460-3

319.1

1.20

75

0.16

460-3

460-3

319.1

1.20

75

0.16

575-3

575-3

315.8

0.95

75

0.13

62ER,ES,

ET,EU

230-3

230-3

452.0

3.40

75

0.33

400-3

460-3

452.0

1.70

75

0.16

460-3

460-3

452.0

1.70

75

0.16

575-3

575-3

465.3

1.40

75

0.13

FLA — Full Load Amps

W — Watts