beautypg.com

Carrier 62E User Manual

Page 19

background image

19

Table 4 — Supply and Exhaust Fans

Electrical Data (cont)

LEGEND

Table 5 — Electric Heat

Electrical Data

LEGEND

FAN

OPTION

62E

CHASSIS

UNIT

V-Ph

FAN MOTOR

V-Ph

W

FLA

Qty

M

K,L,M,

N,P,R

230-3

230-3

2900

7.29

2

400-3

460-3

2900

3.64

2

460-3

460-3

2900

3.64

2

575-3

460-3

2900

2.92

2

N

R,S,

T,U

230-3

230-3

2900

7.29

3

400-3

460-3

2900

3.64

3

460-3

460-3

2900

3.64

3

575-3

460-3

2900

2.92

3

P

T,U

230-3

230-3

2700

6.79

7

400-3

460-3

2700

3.39

7

460-3

460-3

2700

3.39

7

575-3

460-3

2700

2.71

7

R

T,U

230-3

230-3

2700

6.79

8

400-3

460-3

2700

3.39

8

460-3

460-3

2700

3.39

8

575-3

460-3

2700

2.71

8

FLA — Full Load Amps
Qty — Quantity
W

Watts

HEATER

UNIT AND HEATER

V-Ph

62E CHASSIS

kW

FLA

2

17.39

115-1

B,7

8.70

230-1

B,C,2,7

5.03

230-3

B,C,D,E,2,3,4,7

2.51

400-3

B,C,D,E,2,3,4,7

2.51

460-3

B,C,D,E,2,3,4,7

2.01

575-3

B,C,D,E,2,3,4,7

5

43.48

115-1

B,7

21.74

230-1

B,C,2,7

12.57

230-3

B,C,D,E,H,2,3,4,5,7

6.28

400-3

B,C,D,E,H,2,3,4,5,7

6.28

460-3

B,C,D,E,H,2,3,4,5,7

5.03

575-3

B,C,D,E,H,2,3,4,5,7

8

20.11

230-3

D,E,H,3,4,5

10.05

400-3

D,E,H,3,4,5

10.05

460-3

D,E,H,3,4,5

8.04

575-3

D,E,H,3,4,5

10

25.13

230-3

E,H,K,L,4,5,6

12.57

400-3

E,H,K,L,4,5,6

12.57

460-3

E,H,K,L,4,5,6

10.05

575-3

E,H,K,L,4,5,6

15

37.70

230-3

H,K,L,M,N,5,6

18.85

400-3

H,K,L,M,N,5,6

18.85

460-3

H,K,L,M,N,5,6

15.08

575-3

H,K,L,M,N,5,6

20

50.26

230-3

H,K,L,M,N,P,5,6

25.13

400-3

H,K,L,M,N,P,5,6

25.13

460-3

H,K,L,M,N,P,5,6

20.11

575-3

H,K,L,M,N,P,5,6

FLA — Full Load Amps
W