Carrier 62E User Manual
Page 2

2
made with the use of a combination roof curb or by using the
drop in damper box accessory. The combination roof curb is a
single curb that supports both the ERV and the RTU and as
internal supply and exhaust air transitions. The drop in damper
box provides a means to make the supply and exhaust air tran-
sitions below the roof.
Table 1A — Physical Data — SI
LEGEND
UNIT 62E
BA/7A
BC/7C
CC/2C
CD/2D
CG/2G
DD/3D
DG/3G
NOMINAL CAPACITY (L/s)
165
235
470
425
520
615
755
CAPACITY RANGE (L/s)
94-378
94-378
236-543
189-519
236-661
283-755
378-944
MAXIMUM SHIPPING WEIGHT (kg)
150
152
221
228
228
284
284
MAXIMUM OPERATING WEIGHT (kg)
127
130
199
205
205
262
262
UNIT DIMENSIONS (mm)
Length (includes hoods)
1123/1242
1570/1461
1717/1455
Width
790/925
980/1115
1128/1262
Height
879/793
1069/983
1064/1130
ROTARY ENERGY EXCHANGER
Type
Monolithic
Segmented
Size (Diam x Depth) (mm)
483 x 25
483 x 51
635 x 51
635 x 76
762 x 76
Nominal Drive Motor kW
0.07
0.07
0.07
0.07
0.07
SUPPLY/EXHAUST FANS
Type
Centrifugal DWDI
Backward Inclined, Single Width Single Inlet
Drive Type
Direct
EC Motor with Integral Frequency Drive
Fan Option Code
(see fan option table)
A
A, B
C
C
FILTERS
Type
51 mm Pleated
Exhaust Air – Qty...Size (L x W x D) (mm)
1...305 x 610 x 51
1...356 x 635 x 51
2…406 x 635 x 51
Outside Air – Qty...Size (L x W x D) (mm)
1...305 x 610 x 51
1...356 x 635 x 51
2…406 x 635 x 51
UNIT 62E
EB/4B
ED/4D
EF/4F
EG/4G
HB/5B
HD/5D
HF/5F
HG/5G
KD/6D
KG/6G
NOMINAL CAPACITY (L/s)
660
1040
1040
1225
1415
2170
2170
2595
2125
3680
CAPACITY RANGE (L/s)
378-850
519-1227 614-1274 614-1652 661-1700
1038-
2643
1038-
2550
1415-
3492
1180-
2595
1888-
4955
MAXIMUM SHIPPING
WEIGHT (kg)
508
525
508
525
789
803
789
803
1157
1157
MAXIMUM OPERATING
WEIGHT (kg)
485
503
485
503
766
781
766
781
1043
1043
UNIT DIMENSIONS (mm)
Length (includes hoods)
2172/1798
2639/2035
2908/2187
Width
1387/1521
1702/1836
1971/2106
Height
1283/1389
1420/1704
1572/1974
ROTARY ENERGY
EXCHANGER
Type
Segmented
Size (Diam x Depth) (mm)
914 x 38
914 x 76
914 x 38
914 x 76
1321 x
38
1321 x
76
1321 x
38
1321 x
76
1626 x 76
Nominal Drive Motor kW
0.1
0.1
0.1
0.1
0.1
0.1
0.2
SUPPLY/EXHAUST FANS
Type
Backward Inclined, Single Width Single Inlet
Drive Type
EC Motor with Integral Frequency Drive
Fan Option Code
(see fan option table)
C, E
E, F
E, F, L
E, F, L, M
F, L, M
FILTERS
Type
51 mm Pleated
Exhaust Air – Qty...Size
(L x W x D) (mm)
2…508 x 635 x 51
3…508 x 635 x 51
6…406 x 610 x 51
Outside Air – Qty...Size
(L x W x D) (mm)
2…508 x 635 x 51
3…508 x 635 x 51
6…406 x 610 x 51
DWDI — Double Width, Double Inlet
EC