beautypg.com

Carrier 62E User Manual

Page 2

background image

2

made with the use of a combination roof curb or by using the

drop in damper box accessory. The combination roof curb is a

single curb that supports both the ERV and the RTU and as

internal supply and exhaust air transitions. The drop in damper

box provides a means to make the supply and exhaust air tran-

sitions below the roof.

Table 1A — Physical Data — SI

LEGEND

UNIT 62E

BA/7A

BC/7C

CC/2C

CD/2D

CG/2G

DD/3D

DG/3G

NOMINAL CAPACITY (L/s)

165

235

470

425

520

615

755

CAPACITY RANGE (L/s)

94-378

94-378

236-543

189-519

236-661

283-755

378-944

MAXIMUM SHIPPING WEIGHT (kg)

150

152

221

228

228

284

284

MAXIMUM OPERATING WEIGHT (kg)

127

130

199

205

205

262

262

UNIT DIMENSIONS (mm)

Length (includes hoods)

1123/1242

1570/1461

1717/1455

Width

790/925

980/1115

1128/1262

Height

879/793

1069/983

1064/1130

ROTARY ENERGY EXCHANGER

Type

Monolithic

Segmented

Size (Diam x Depth) (mm)

483 x 25

483 x 51

635 x 51

635 x 76

762 x 76

Nominal Drive Motor kW

0.07

0.07

0.07

0.07

0.07

SUPPLY/EXHAUST FANS

Type

Centrifugal DWDI

Backward Inclined, Single Width Single Inlet

Drive Type

Direct

EC Motor with Integral Frequency Drive

Fan Option Code
(see fan option table)

A

A, B

C

C

FILTERS

Type

51 mm Pleated

Exhaust Air – Qty...Size (L x W x D) (mm)

1...305 x 610 x 51

1...356 x 635 x 51

2…406 x 635 x 51

Outside Air – Qty...Size (L x W x D) (mm)

1...305 x 610 x 51

1...356 x 635 x 51

2…406 x 635 x 51

UNIT 62E

EB/4B

ED/4D

EF/4F

EG/4G

HB/5B

HD/5D

HF/5F

HG/5G

KD/6D

KG/6G

NOMINAL CAPACITY (L/s)

660

1040

1040

1225

1415

2170

2170

2595

2125

3680

CAPACITY RANGE (L/s)

378-850

519-1227 614-1274 614-1652 661-1700

1038-

2643

1038-

2550

1415-

3492

1180-

2595

1888-

4955

MAXIMUM SHIPPING
WEIGHT (kg)

508

525

508

525

789

803

789

803

1157

1157

MAXIMUM OPERATING
WEIGHT (kg)

485

503

485

503

766

781

766

781

1043

1043

UNIT DIMENSIONS (mm)

Length (includes hoods)

2172/1798

2639/2035

2908/2187

Width

1387/1521

1702/1836

1971/2106

Height

1283/1389

1420/1704

1572/1974

ROTARY ENERGY
EXCHANGER

Type

Segmented

Size (Diam x Depth) (mm)

914 x 38

914 x 76

914 x 38

914 x 76

1321 x

38

1321 x

76

1321 x

38

1321 x

76

1626 x 76

Nominal Drive Motor kW

0.1

0.1

0.1

0.1

0.1

0.1

0.2

SUPPLY/EXHAUST FANS

Type

Backward Inclined, Single Width Single Inlet

Drive Type

EC Motor with Integral Frequency Drive

Fan Option Code
(see fan option table)

C, E

E, F

E, F, L

E, F, L, M

F, L, M

FILTERS

Type

51 mm Pleated

Exhaust Air – Qty...Size
(L x W x D) (mm)

2…508 x 635 x 51

3…508 x 635 x 51

6…406 x 610 x 51

Outside Air – Qty...Size
(L x W x D) (mm)

2…508 x 635 x 51

3…508 x 635 x 51

6…406 x 610 x 51

DWDI — Double Width, Double Inlet
EC

Electronically Commutated