Step 6 — rig and place unit, Caution, Warning – Carrier 62E User Manual
Page 16
16
manufactured duct and attach to the supply and exhaust open-
ings on the horizontal box.
Step 6 — Rig and Place Unit —
To transfer the unit
from the shipping platform to the storage or installation site, re-
fer to the rigging label on the unit and these instructions.
Refer to Tables 1A and 1B for ERV unit weights. Check lift-
ing devices for capacity constraints.
Hook rigging shackles through the eyehooks in the ERV
unit. Connect lifting straps and spreader bars. See Fig 13.
Spreader bars must be positioned to prevent cables from rub-
bing against the ERV unit.
Carefully lift the ERV unit and set on ERV roof curb. Do
not drop the ERV unit onto the roof curb, as damage may oc-
cur. Avoid twisting or uneven lifting of the unit. Never lift the
unit by the hoods or any means other than the provided lifting
holes or eyes.
CAUTION
All panels must be in place when rigging. Unit is not
designed for handling by fork truck. Damage to unit may
result.
WARNING
Never attempt to lift the ERV in any way that does not use
all four (4) eyehooks. Lifting the unit with an uneven distri-
bution of the weight may cause damage to the unit and/or
personal injury or death.
IMPORTANT: Remove the fork pockets from the ERV
unit before setting it on the roof curb.
FORK POCKETS (REMOVE
BEFORE INSTALLING ON CURB)
62E UNIT
TYPE
DIMENSIONS (in.)
A
B
C
D
E
B
27.221
12.111
8.750
14.000
22.604
C
34.721
15.861
12.500
14.000
22.604
D
40.521
18.761
15.400
18.000
26.600
E
50.721
23.861
20.500
21.000
29.604
H
63.141
30.071
26.710
24.000
32.604
K
72.721
34.861
31.500
26.022
34.637
L
78.721
37.861
34.500
26.022
34.637
M
85.721
41.361
38.000
26.022
34.637
N
91.721
44.361
41.000
31.011
39.615
P
96.721
46.861
43.500
33.052
41.682
R
104.721
50.861
47.500
33.052
41.682
S
108.721
52.861
49.500
35.110
43.769
T
115.721
56.361
53.000
35.110
43.769
U
115.721
56.361
53.000
35.110
43.769
a62-379
Fig. 12 — 62EB-62EU Unit Horizontal Discharge Box Dimensions