Carrier 62E User Manual

Page 29

background image

29

Table 8 — MS/TP Wiring Recommendations

LEGEND

TO ADDRESS THE UPC OPEN CONTROLLER — The

user must give the UPC Open controller an address that is

unique on the BACnet network. Perform the following proce-

dure to assign an address:

1. If the UPC Open controller is powered, pull the screw ter-

minal connector from the controller's power terminals la-

beled Gnd and HOT. The controller reads the address

each time power is applied to it.

2. Using the rotary switches (see Fig. 25 and 28), set the

controller's address. Set the Tens (10's) switch to the tens

digit of the address, and set the Ones (1's) switch to the

ones digit.

As an example in Fig. 28, if the controller’s address is 25,

point the arrow on the Tens (10's) switch to 2 and the arrow on

the Ones (1's) switch to 5.

BACNET DEVICE INSTANCE ADDRESS — The UPC

Open controller also has a BACnet Device Instance address.

This Device Instance MUST be unique for the complete BAC-

net system in which the UPC Open controller is installed. The

Device Instance is auto generated by default and is derived by

SPECIFICATION

RECOMMMENDATION

Cable

Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable

Conductor

22 or 24 AWG stranded copper (tin plated)

Insulation

Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.

Color Code

Black/White

Twist Lay

2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal

Shielding

Aluminum/Mylar shield with 24 AWG TC drain wire

Jacket

SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.

DC Resistance

15.2 Ohms/1000 feet (50 Ohms/km) nominal

Capacitance

12.5 pF/ft (41 pF/meter) nominal conductor to conductor

Characteristic Impedance

100 Ohms nominal

Weight

12 lb/1000 feet (17.9 kg/km)

UL Temperature Rating

SmokeGard 167°F (75°C), Halar -40 to 302°F (-40 to 150°C)

Voltage

300 Vac, power limited

Listing

UL: NEC CL2P, or better

Fig. 27 — BT485 Terminator Installation

AWG

American Wire Gage

CL2P

Class 2 Plenum Cable

DC

Direct Current

FEP

Fluorinated Ethylene Polymer

NEC

National Electrical Code

O.D.

Outside Diameter

TC

Tinned Copper

UL

Underwriters Laboratories

10's

1's

1

3

45

2

7

8

9

6

0

1

3

45

2

7

8

9

6

0

Fig. 28 — Address Rotary Switches