Green light expr ess, Glpx panels – Crestron electronic Green Light GLPS-HSW-FT User Manual
Page 34
Crestron Commercial Lighting Design Guide
30
G
reen Light
Expr
ess
GLPX Panels
Crestron GLPX panels are configurable for dimming or switching and come
equipped with Green Light Express modules.
When specifying and ordering a GLPX panel, construct a model name as
shown to the right. Possible choices are listed underneath each blue box.
The numbered steps below describe each choice in detail.
Examples: GLPX-HSW-16
GLPX-HDSW-56
1. Module Type
GLPX-___-
Use the table to determine the type of dimming or switching module required.
___
Modules
SW
HSW
HDSW
FLV
2DIM8
Module Types
High-inrush
Switching
Arcless High-
inrush Switching
Heavy Duty
Switching
0-10V Dimming
Dimming
Voltages
120/230/277
120/230/277
120/230/277
120/230/277
120/230/277
Lighting Output
Capacity
16A
16A
20A
16A
16A
Motor Output Capacity
(120/230/277 V)
1/2/2 hp
0.5/1/1 hp
0.5/1.5/1.5 hp
0.5/1.5/1.5
0.5/1/1 hp
Rated Relay Lifetime
Up to 100,000
1,000,000
30,000
1,000,000
1,000,000
Additional Info
Page 31
Page 26
Page 32
Page 27
Page 34
2. Number of Loads
GLPX-___-
Find the row in the table that matches your choice in step 1. In that row is the maximum number of loads for each cabinet size.
___
Cabinet Size
Small
Medium
Large
M
a
ximum # of
L
o
ads
SW
8
24
56
HSW
8
16
32
HDSW
8
24
56
FLV
-
8
16
2DIM8
8
16
32
Height
12 5/16 in (31.24 cm)
24 1/4 in (61.60 cm)
39 21/32 in (100.71 cm)
Width
14 1/8 in (35.89 cm)
16 1/8 in (40.89 cm)
16 1/8 in (40.89 cm)
Depth
4 3/8 in (11.08 cm)
4 7/16 in (11.23 cm)
4 7/16 in (11.23 cm)
Note: If using 3-wire fluorescent dimming with the 2DIM8, the actual number of loads will be half the specified amount. For
example, a panel specified for 16 2DIM8 loads can control up to eight 3-wire ballasts.
What is Arcless Switching?
Crestron offers two switching relay types: high-inrush and arcless high-inrush. Arcless high-inrush relays use a TRIAC to handle the
current turn on. Within milliseconds, the continuous load is transferred from the TRIAC to a robust 50A mechanically-latching relay.
All switching occurs at the zero-cross point of the AC waveform under microprocessor control. This is a complete solution
eliminating arcing at the physical relay contacts during turn on and turn off. By eliminating arcing, the relay lifetime is increased
substantially.
GLPX
Module
Type
Number of
Loads
-
-
1
2
3
...
54
55
56
SW
HSW
HDSW
FLV
2DIM8
GLPX Model Naming System