beautypg.com

Crestron electronic Crestron iLux CLS-C6 series User Manual

Cls-exp-dimu functional summary, Specifications

background image

CLS-EXP-DIMU

Functional Summary

Crestron Electronics, Inc.

Installation Guide – DOC. 6682B

15 Volvo Drive Rockleigh, NJ 07647

(2020684)

The CLS-EXP-DIMU enables the expansion of the
Crestron iLux™ Integrated Lighting System (CLS-C6
series) and other Crestron lighting dimmers to allow
dimming of both forward and reverse phase type loads.
Supported loads include electronic low-voltage, magnetic
low-voltage, incandescent, neon/cold cathode, or 2-wire
dimmable fluorescent. A single model supports 120, 230,
or 277 Volt loads up to 16 Amps.

The CLS-EXP-DIMU simplifies installation by auto-
detecting the dimmable load type connected to it and
selecting the appropriate dimming mode to control that
load. Reverse phase (trailing edge) dimming supports
incandescent and electronic low-voltage load types, while
forward phase (leading edge) dimming handles magnetic
low-voltage, neon, and other inductive load types.

Any output channel of the iLux system can be used to
control the CLS-EXP-DIMU to dim a fully loaded circuit.
It is also compatible with CLW-Series

1

in-wall dimmers

and select CLX-Series lighting control modules. The
metal enclosure is designed for mounting to a vertical
surface and can be installed in a space used for
environmental air as defined in NEC Article 300.22(C).
Conduit knockouts are provided on the bottom and lower
sides. All connections are made via screw terminals
behind the front cover.

• Works with Crestron iLux (CLS-C6 series),

DIN-1DIMU4, CLW

1

Series, and CLX Series

dimmers

• Emulates the characteristics of the dimmer that is

controlling it

• Up to five Expansion Modules can be connected

to a single dimmer output

• Supports 120, 230, and 277 Volt ELV, MLV,

NCC, incandescent, and 2-wire dimmable
fluorescent loads

• Auto-selects for forward or reverse phase

• Can be installed in an air-handling space

2

• Includes threshold adjustment for setting

minimum fluorescent dimming level

• Built-in air gap relay at the output
• Surface mount design

1.

CLW-Series devices must have a dedicated neutral.

2.

As defined in NEC Article 300.22(C).

CLS-EXP-DIMU Physical View

Specifications

CLS-EXP-DIMU Specifications

SPECIFICATION DETAILS

Load Ratings

Output

Channels

Load

Rating

Minimum

Load

at 120 Volts
at 230 Volts
at 277 Volts

Load

Types

1

16 Amps


15 Watts
25 Watts
30 Watts

Electronic Low Voltage,
Incandescent, Neon/Cold
Cathode, Magnetic Low Voltage,
2-Wire Dimmable Fluorescent
(Advance Mark 10 Powerline

®

or

equivalent)

Maximum Modules per
Dimmer Output

5

Input Voltages

Line

Power

Control

Input

120 to 277 Volts AC, 50/60 Hz

120 or 230 Volts AC, 50/60 Hz,
phase independent of line power
and load, presents 25 Watts load
to the controlling device

Electrical Terminals

Captive screw type;
Accommodates two 22-12 AWG
(0.34-4.0 mm

2

) wires

(Continued on following page.)

Tel: 888.CRESTRON

02.09

Fax: 201.767.7576

Specifications subject to

www.crestron.com