APPENDIX 1: INPUT WIRING REQUIREMENTS
NOTES
Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
Cable size is de-rated based on the Duty Cycle of the equipment.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations
refer to local or national codes.
Cable conductor temperature used is 167° F (75° C).
An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should be
used to minimize damage to Plasma Cutting, Welding or power distribution equipment.
NEVER
use replaceable element fuses like UL Class H, or "one-time" fuses like UL Class K5.
Input
Power Input
Current
Suggested Sizes (See Notes)
Voltage
Freq.
3-Ph
3-Ph
Fuse (Amps)
Wire (AWG)
Wire (Canada)
(Volts)
(Hz)
(kVA)
(Amps)
3-Ph
3-Ph
3-Ph
208
50/60
28.1
78
100
2
2
220
50/60
28.6
75
100
2
2
230
50/60
29.5
74
100
2
2
240
50/60
29.9
72
90
2
2
380
50/60
29.0
44
60
6
6
415
50/60
29.5
41
60
6
6
460
50/60
29.5
37
50
6
6
575
Requires Transformer Module
Line Voltages with Suggested Circuit Protection and Wire Sizes
Based on National Electric Code and Canadian Electrical Code