Appendix i: input wiring requirements – Tweco PakMaster 100XL Plus User Manual
Page 37
Manual 0-2784
31
APPENDIX
APPENDIX I: INPUT WIRING REQUIREMENTS
NOTES
The table above is based on the following output current & voltage: 140VDC @ 80A
Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
Cable size is de-rated based on the Duty Cycle of the equipment.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations
refer to local or national codes.
Cable conductor temperature used is 167° F (75° C).
An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should be
used to minimize damage to Plasma Cutting, Welding or power distribution equipment.
NEVER
use replaceable element fuses like UL Class H, or "one-time" fuses like UL Class K5.
Flexible cable must have an outside diameter of 0.69 inches (17.5 mm) or greater.
Input
Power Input Current Input
Voltage
Freq.
3-Ph
3-Ph
Fuse (Amps)
Wire (mm
2
)
(Volts)
(Hz)
(kVA)
(Amps)
3-Ph
3-Ph
380
50/60
19.1
29
35
10
415
50/60
19.4
27
35
10
Line Voltages with Suggested Circuit Protection and Wire Sizes
Suggested Sizes (see notes)