Step 3 — Locate Unit

— The following guidelines

should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
• Locate in areas where ambient temperatures are between

39 F and 102 F and relative humidity is no greater than

75%.

• Provide sufficient space for water, electrical and duct

connections.

• Locate unit in an area that allows easy access and removal

of filter and access panels.

• Allow enough space for service personnel to perform

maintenance.

• Return air must be able to freely enter the space if unit needs

to be installed in a confined area such as a closet.
NOTE: Correct placement of the horizontal unit can play an

important part in minimizing sound problems. Since

ductwork is normally applied to these units, the unit can be

placed so that the principal sound emission is outside the oc-

cupied space in sound-critical applications. A fire damper

may be required by the local code if a fire wall is penetrated.

FIELD CONVERSION OF DISCHARGE AIR — The dis-

charge air of the 50PSH horizontal units can be converted

between side and back discharge in the field. The conversion

process is the same for right and left return configurations. See

Fig. 7 and 8.
NOTE: It is not possible to convert return air between left or

right return models in the field due to refrigerant piping

changes.

Return

Air

Power

Thermostat
Wiring

Compressor
Access Panel

Balancing Valve
(field-installed
accessory)

Low Pressure
Drop Water

Control Valve
(optional)
(field-installed
accessory)

Ball Valve with optional

integral P/T plug
(typical for supply and
return piping) (field-Installed
accessory)

Water
Out

Water
In

Building
Loop

Supply Air

Flexible
Connection


Stainless steel
braid hose

with integral
“J” swivel
(field-installed
accessory)

Return

Air

Power

Thermostat

Wiring

Compressor

Access Panel

Balancing Valve

(field-installed

accessory)

Low Pressure
Drop Water
Control Valve
(optional)
(field-installed
accessory)

Ball Valve with
optional integral
P/T plug (typical for
supply and return
piping)(field-installed
accessory)

Water

Out

Water

In

Building

Loop

Supply Air

Flexible

Connection

Flexible

Connection

Stainless
steel
braid hose
with
integral ”J”
swivel(field-
installed
accessory)

NOTE: Ball valve with integral pressure temperature plug recommended.

Fig. 5 — Typical Vertical Installation — 50PSV Unit

NOTE: Ball valve with integral pressure temperature plug recommended.

Fig. 6 — Typical Downflow Installation —

50PSD Unit

A50-7730

A50-7729

Return Air

Remove Screws

Return Air

Rotate

Move to Side

Side Discharge

Return Air

Discharge Air

Drain

Back Discharge

Replace Screws

Water

Connection End

Water

Connection End

Water

Connection End

Fig. 7 — Conversion Left Return,

Side Discharge to Back Discharge

A50-6256

Water

Connection End

Supply
Duct

Return Air

Water

Connection End

Drain

Return Air

Discharge Air

Side Discharge

Back Discharge

Fig. 8 — Conversion Right Return,
Side Discharge to Back Discharge

A50-6257