beautypg.com

Step 9 — wire field controls, Fig. 29 — typical accessory wiring – Carrier AQUAZONE PSV User Manual

Page 27

background image

27

Step 9 — Wire Field Controls

THERMOSTAT CONNECTIONS — The thermostat should

be wired directly to the ECM control board. See Fig. 27.
WATER FREEZE PROTECTION — The Aquazone™ con-

trol allows the field selection of source fluid freeze protection

points through jumpers. The factory setting of jumper JW3

(FP1) is set for water at 30 F. In earth loop applications, jumper

JW3 should be clipped to change the setting to 10 F when us-

ing antifreeze in colder earth loop applications. See Fig. 28.
NOTE: The extended range option should be selected

with water temperatures below 60 F to prevent internal

condensation.
AIR COIL FREEZE PROTECTION — The air coil freeze

protection jumper JW2 (FP2) is factory set for 30 F and should

not need adjusting.
ACCESSORY CONNECTIONS — Terminal A on the control

is provided to control accessory devices such as water valves,

electronic air cleaners, humidifiers, etc. This signal operates

with the compressor terminal. See Fig. 29. Refer to the specific

unit wiring schematic for details.
NOTE: The A terminal should only be used with 24-volt

signals — not line voltage signals.

WATER SOLENOID VALVES — An external solenoid

valve(s) should be used on ground water installations to shut

off flow to the unit when the compressor is not operating. A

slow closing valve may be required to help reduce water

hammer. Figure 29 shows typical wiring for a 24-vac external

solenoid valve. Figures 30 and 31 illustrate typical slow closing

water control valve wiring for Taco 500 Series and Taco ESP

Series valves. Slow closing valves take approximately 60 sec.

to open (very little water will flow before 45 sec.). Once fully

open, an end switch allows the compressor to be energized

(only on valves with end switches). Only relay or triac based

electronic thermostats should be used with slow closing valves.

When wired as shown, the slow closing valve will operate

properly with the following notations:

1. The valve will remain open during a unit lockout.
2. The valve will draw approximately 25 to 35 VA through

the “Y” signal of the thermostat.

IMPORTANT: Connecting a water solenoid valve can

overheat the anticipators of electromechanical thermo-

stats. Only use relay based electronic thermostats.

Fig. 27 — Low Voltage Field Wiring

COMPLETE C CONTROL

CAPACITOR

LINE

LO

AD

COMPRESSOR CONTACTOR

TRANSFORMER

Y

GGGG

R

W

O

Y2

Y1

G

R

C

Y2 Y1 G

O W C R DH AL1 A

A

AL1

SW1
SW2
SW3
SW4

SW5
SW6
SW7

SW8
SW9

OFF

ON

G DEHUM

CFM

TB1

J1

S1

THERMOSTAT CONNECTION

TYPICAL
WATER
VALVE

C

A

24 VAC

TERMINAL STRIP P2

Fig. 29 — Typical Accessory Wiring

A50-6269

AQUAZONE CONTROL (Complete C Shown)

Fig. 28 — Typical Aquazone™ Control Board

Jumper Locations

A50-7764

a50-8197

This manual is related to the following products: