Carrier AQUAZONE PSV User Manual
Page 38

38
Table 25 — 50PSH, PSV, PSD030 Typical Unit Operating Pressures and Temperatures
LEGEND
Table 26 — 50PSH, PSV, PSD036 Typical Unit Operating Pressures and Temperatures
LEGEND
Table 27 — 50PSH, PSV, PSD042 Typical Unit Operating Pressures and Temperatures
LEGEND
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
FULL LOAD COOLING — WITHOUT HWG ACTIVE
FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5
116-126
146-166
27-32
7-13
19.6-21.6
16-22
69- 79
275-295
7-12
6-11
7.2- 9.2
16-22
2.25
115-125
138-158
27-32
6-11
14.3-16.3
17-23
73- 83
277-297
7-12
6-11
5.4- 7.4
17-23
3
115-125
128-148
27-32
6-11
8.0-10.0
17-23
76- 86
279-299
7-12
6-11
3.5- 5.5
17-23
50
1.5
129-139
217-237
12-17
6-11
20.8-22.8
17-23
96-106
300-320
10-15
9-14
10.5-12.5
21-27
2.25
128-138
203-223
12-17
5-10
15.0-17.0
18-24
100-110
304-324
10-15
9-14
7.6- 9.6
22-28
3
128-138
189-209
12-17
5-10
9.2-11.2
18-24
105-115
309-329
10-15
9-14
4.8- 6.8
22-28
70
1.5
132-142
293-313
9-14
6-11
20.1-22.1
17-23
123-133
327-347
11-16
11-16
13.2-15.2
25-32
2.25
131-141
274-294
9-14
5-10
14.4-16.4
18-24
129-139
333-353
11-16
11-16
9.8-11.8
26-33
3
131-141
256-276
9-14
5-10
8.6-10.6
18-24
135-145
339-359
11-16
11-16
6.4- 8.4
27-34
90
1.5
137-147
383-403
7-12
5-10
19.4-21.4
16-22
155-165
355-375
13-18
11-16
16.8-18.8
30-38
2.25
137-147
362-382
7-12
5-10
13.8-15.8
16-22
162-172
362-382
14-19
11-16
12.7-14.7
31-39
3
137-147
342-362
7-12
5-10
8.2-10.2
16-22
169-179
369-389
16-21
11-16
8.6-10.6
32-40
110
1.5
143-153
475-495
6-11
9-14
18.2-20.2
16-22
—
—
—
—
—
—
2.25
143-153
457-477
6-11
6-11
13.0-14.0
16-22
—
—
—
—
—
—
3
143-153
439-459
6-11
6-11
7.7- 9.7
16-22
—
—
—
—
—
—
DB
— Dry Bulb
HWG — Hot Water Generator
—
— No Heating Operation in This Temperature Range
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
FULL LOAD COOLING — WITHOUT HWG ACTIVE
FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5
117-127
142-162
33-38
8-14
19.1-21.1
15-22
69- 79
276-296
10-15
10-15
7.2- 9.2
17-23
2.25
116-126
134-154
33-38
7-12
13.8-15.8
15-22
73- 83
278-298
10-15
10-15
5.3- 7.3
18-24
3
116-126
124-144
33-38
7-12
7.4- 9.4
15-22
76- 86
280-300
10-15
10-15
3.5- 5.5
18-24
50
1.5
136-146
211-231
11-16
6-11
20.6-22.6
17-23
99-109
302-322
10-15
13-18
10.6-12.6
22-28
2.25
136-146
197-217
11-16
5-10
14.8-16.8
17-23
103-113
306-326
10-15
13-18
7.7- 9.7
23-29
3
136-146
183-203
11-16
5-10
9.0-11.0
17-23
108-118
311-331
10-15
13-18
5.0- 7.0
23-29
70
1.5
137-147
275-295
9-14
10-15
19.0-21.0
18-24
127-137
332-352
10-15
15-20
13.5-15.5
27-34
2.25
137-147
260-280
9-14
9-14
13.8-15.8
19-25
133-143
338-358
10-15
15-20
10.1-12.1
28-35
3
137-147
245-265
9-14
9-14
8.0-10.0
19-25
139-149
344-364
10-15
15-20
6.7- 8.7
29-36
90
1.5
142-152
373-393
7-12
10-15
19.5-21.5
17-23
164-174
365-385
11-16
15-20
17.4-19.4
34-42
2.25
142-152
352-372
8-13
6-11
13.9-15.9
17-23
172-182
372-392
11-16
15-20
13.2-15.2
35-43
3
142-152
332-352
8-13
6-11
8.3-10.3
17-23
181-191
379-399
12-17
15-20
9.0-11.0
36-44
110
1.5
147-157
467-487
6-11
10-15
16.2-18.2
16-22
—
—
—
—
—
—
2.25
147-157
448-468
6-11
8-13
11.9-13.9
16-22
—
—
—
—
—
—
3
147-157
430-450
6-11
7-12
7.6- 9.6
16-22
—
—
—
—
—
—
DB
— Dry Bulb
HWG — Hot Water Generator
—
— No Heating Operation in This Temperature Range
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
FULL LOAD COOLING — WITHOUT HWG ACTIVE
FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5
114-124
170-190
27-32
10-15
17.2-19.2
17-23
69- 79
286-306
5-10
5-10
4.5- 6.5
16-22
2.25
113-123
150-170
27-32
9-14
12.7-14.7
17-23
72- 82
289-309
5-10
6-11
3.9- 5.9
17-23
3
113-123
131-151
27-32
7-12
8.2-10.2
17-23
75- 85
292-312
6-11
6-11
3.2- 5.2
18-24
50
1.5
130-140
226-246
10-15
6-11
17.8-19.8
20-26
100-110
315-335
7-12
6-11
9.0-11.0
22-28
2.25
129-139
208-228
10-15
5-10
13.3-15.3
20-26
105-115
322-342
8-13
6-11
7.0- 9.0
23-29
3
129-139
190-210
10-15
4- 9
8.8-10.8
20-26
110-120
330-350
10-15
7-12
5.0- 7.0
24-30
70
1.5
132-142
290-310
6-11
6-11
17.3-19.3
19-25
131-141
347-367
11-16
6-11
13.4-15.4
29-35
2.25
131-141
273-293
6-11
5-10
12.8-14.8
19-25
138-148
358-378
13-18
8-13
10.0-12.0
30-36
3
131-141
255-275
6-11
4- 9
8.3-10.3
19-25
145-155
369-389
16-21
9-14
6.9- 8.9
31-37
90
1.5
136-146
370-390
6-11
6-11
16.0-18.0
17-23
175-185
393-413
19-24
7-12
17.6-19.6
36-42
2.25
135-145
350-370
6-11
5-10
11.8-13.8
17-23
177-187
401-421
20-25
9-14
13.2-15.2
37-43
3
135-145
330-350
6-11
4- 9
7.6- 9.6
17-23
180-190
409-429
22-27
12-17
8.7-10.7
38-44
110
1.5
143-153
469-489
6-11
6-11
14.0-16.0
16-22
—
—
—
—
—
—
2.25
142-152
448-468
6-11
5-10
11.0-13.0
16-22
—
—
—
—
—
—
3
141-151
427-447
6-11
4- 9
7.0- 9.0
16-22
—
—
—
—
—
—
DB
— Dry Bulb
HWG — Hot Water Generator
—
— No Heating Operation in This Temperature Range