Wshp open test mode, Retry mode, Aquazone™ deluxe d control led indica- tors – Carrier AQUAZONE PSV User Manual

Page 47

background image

47

Table 35 — Complete C Control LED Code and

Fault Descriptions

LEGEND

WSHP Open Test Mode —

To enter WSHP Open test

mode, navigate from the BACview

6

home screen to the config-

uration screen. Choose the service screen and enable unit test.

The controller will then test the following:
FAN TEST — Tests all fan speeds, sequences fan from low to

high, and operates each speed for one minute. Resets to disable

on completion.
COMPRESSOR TEST — Tests compressor cooling and

heating operation. Sequences cooling stage 1 then cooling

stage 2 followed by heating stage 2 then reduces capacity to

heating stage 1. Operates for 1 minute per step.
DEHUMIDIFICATION TEST — Tests dehumidification

mode. Operates for 2 minutes.

AUXILIARY HEATING TEST — Tests auxiliary heat.

Sequences fan on and enables heating coil for 1 minute.
H

2

O ECONOMIZER TEST — Tests entering/returning

water loop economizer operation. Sequences fan and opens

economizer water valve for one minute.
OPEN VENT DAMPER 100% TEST — Tests outside air

(OA) damper operation.
PREPOSITION OA DAMPER — Prepositions OA damper

actuator to set proper preload.
NOTE: The auxiliary heating test, H

2

O economizer test, open

vent damper 100% test, and preposition OA damper features

will not be visible on the screen unless configured.
Once tests are complete, set unit test back to disable. Unit will

automatically reset to disable after 1 hour.

Retry Mode —

In Retry mode, the status LED will start to

flash slowly to signal that the control is trying to recover from

an input fault. The control will stage off the outputs and try to

again satisfy the thermostat used to terminal Y. Once the ther-

mostat input calls are satisfied, the control will continue normal

operation.
NOTE: If 3 consecutive faults occur without satisfying the

thermostat input call to terminal Y, the control will go into

lockout mode. The last fault causing the lockout is stored in

memory and can be viewed by entering Test mode.

Aquazone™ Deluxe D Control LED Indica-
tors —

There are 3 LED indicators on the Deluxe D control:

STATUS LED — Status LED indicates the current status or

mode of the D control. The Status LED light is green.
TEST LED — Test LED will be activated any time the D

control is in test mode. The Test LED light is yellow.
FAULT LED — Fault LED light is red. The fault LED will

always flash a code representing the last fault in memory. If

there is no fault in memory, the fault LED will flash code 1 and

appear as one fast flash alternating with a 10-second pause. See

Table 36.

Table 36 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations

LEGEND

NOTES:
1. If there is no fault in memory, the Fault LED will flash code 1.
2. Codes will be displayed with a 10-second Fault LED pause.
3. Slow flash is 1 flash every 2 seconds.
4. Fast flash is 2 flashes every 1 second.
5. EXAMPLE: “Flashing Code 2” is represented by 2 fast flashes followed by

a 10-second pause. This sequence will repeat continually until the fault is
cleared.

LED CODE

FAULT

DESCRIPTION

1

No fault in memory

There has been no fault since the
last power-down to power-up
sequence

2

High-Pressure Switch

HP switch opens instantly

3

Low-Pressure Switch

LP switch opens for 30 continu-
ous seconds before or during a
call (bypassed for first
60 seconds)

4

Freeze Protection Coax —
FP1

FP1 below Temp limit for
30 continuous seconds (bypassed
for first 60 seconds of operation)

5

Freeze Protection Air Coil —
FP2

FP2 below Temp limit for
30 continuous seconds (bypassed
for first 60 seconds of operation)

6

Condensate overflow

Sense overflow (grounded) for
30 continuous seconds

7

(Autoreset)

Over/Under Voltage
Shutdown

“R” power supply is <19VAC or
>30VAC

8

PM Warning

Performance Monitor Warning
has occurred.

9

FP1 and FP2
Thermistors are swapped

FP1 temperature is higher than
FP2 in heating/test mode, or FP2
temperature is higher than FP1 in
cooling/test mode.

FP

Freeze Protection

LP

Low Pressure

HP

High Pressure

PM

Performance Monitor

LED

Light-Emitting Diode

DESCRIPTION

STATUS LED

(Green)

TEST LED

(Yellow)

FAULT LED (Red)

ALARM RELAY

Normal Mode

On

Off

Flash Last Fault Code in Memory

Open

Normal Mode with PM

On

Off

Flashing Code 8

Cycle (closed 5 sec,

open 25 sec, …)

Deluxe D Control
is non-functional

Off

Off

Off

Open

Test Mode

On

Flash Last Fault Code in Memory

Cycling Appropriate Code

Night Setback

Flashing Code 2

Flash Last Fault Code in Memory

ESD

Flashing Code 3

Flash Last Fault Code in Memory

Invalid T-stat Inputs

Flashing Code 4

Flash Last Fault Code in Memory

No Fault in Memory

On

Off

Flashing Code 1

Open

HP Fault

Slow Flash

Off

Flashing Code 2

Open

LP Fault

Slow Flash

Off

Flashing Code 3

Open

FP1 Fault

Slow Flash

Off

Flashing Code 4

Open

FP2 Fault

Slow Flash

Off

Flashing Code 5

Open

CO Fault

Slow Flash

Off

Flashing Code 6

Open

Over/Under Voltage

Slow Flash

Off

Flashing Code 7

Open (closed after 15 minutes)

HP Lockout

Fast Flash

Off

Flashing Code 2

Closed

LP Lockout

Fast Flash

Off

Flashing Code 3

Closed

FP1 Lockout

Fast Flash

Off

Flashing Code 4

Closed

FP2 Lockout

Fast Flash

Off

Flashing Code 5

Closed

CO Lockout

Fast Flash

Off

Flashing Code 6

Closed

CO

Condensate Overflow

HP

High Pressure

ESD — Emergency Shutdown

LP

Low Pressure

FP

Freeze Protection

PM

Performance Monitor