Carrier AQUAZONE PSV User Manual
Page 30

30
DEHUMIDIFICATION MODE — The dehumidification mode
setting provides field selection of humidity control. When oper-
ating in the normal mode, the cooling airflow settings are deter-
mined by the cooling tap setting in Table 11. When dehumidifi-
cation is enabled, there is a reduction in airflow in cooling to in-
crease the moisture removal of the heat pump. The
Dehumidification mode can be enabled in two ways:
1. Constant Dehumidification mode: When the Dehumidifi-
cation mode is selected via DIP switch, the ECM will
operate with a multiplier applied to the cooling CFM
settings (approximately 20 to 25% lower airflow). Any
time the unit is running in the Cooling mode, it will oper-
ate at the lower airflow to improve latent capacity. The
“DEHUM” LED will be illuminated at all times. Heating
airflow is not affected.
NOTE: Do not select Dehumidification mode if cooling
setting is tap 1.
2. Automatic (humidistat-controlled) Dehumidification
mode: When the Dehumidification mode is selected
via DIP switch AND a humidistat is connected to termi-
nal DH, the cooling airflow will only be reduced when
the humidistat senses that additional dehumidification is
required. The DH terminal is reverse logic. Therefore,
a humidistat (not dehumidistat) is required. The
“DEHUM” LED will be illuminated only when the humi-
distat is calling for Dehumidification mode. Heating
airflow is not affected.
NOTE: Do not select Dehumidification mode if cooling
setting is tap 1.
Table 11 — ECM Blower Motor Performance Data
LEGEND
NOTES:
1. Factory setting is Tap Setting 2.
2. Airflow is controlled within 5% up to the Max ESP shown with
wet coil.
3. Do not select Dehumidification mode if Tap Setting is on
Setting 1.
4. All units are ARI/ISO (Air Conditioning & Refrigeration Institute/
International Organization for Standardization) 13256-1 rated
Tap Setting 3.
5. Airflow in cfm with wet coil and clean air filter.
6. Units have an ECM (electronically commuted motor) fan motor
as a standard feature. The small additional pressure drop of
the reheat coil causes the ECM motor to slightly increase rpm
to overcome the added pressure drop and maintain selected
cfm up to maximum ESP (external static pressure).
7. Unit sizes 006-012 are not available with ECM motors.
50PS
UNIT
SIZE
MAX
ESP
(in. wg)
FAN
MOTOR
(hp)
TAP
SETTING
COOLING MODE
(cfm)
DEHUMIDIFICATION MODE
(cfm)
HEATING MODE
(cfm)
Stage 1
Stage 2
Fan
Stage 1
Stage 2
Fan
Stage 1
Stage 2
Fan
018
0.50
1
/
2
4
750
620
380
590
480
380
750
620
380
3
700
570
350
550
450
350
700
570
350
2
620
510
310
480
400
310
620
510
310
1
530
430
270
—
—
—
530
430
270
024
0.50
1
/
2
4
950
780
470
740
610
470
1060
870
470
3
850
700
420
660
540
420
950
780
420
2
730
600
360
570
470
360
820
670
360
1
610
500
300
—
—
—
690
570
300
030
0.50
1
/
2
4
1130
920
560
880
720
560
1230
1000
560
3
1000
820
500
780
640
500
1100
900
500
2
880
720
440
680
560
440
980
800
440
1
750
620
380
—
—
—
850
700
380
036
0.50
1
/
2
4
1400
1150
700
1090
900
700
1400
1150
700
3
1250
1020
630
980
800
630
1250
1020
630
2
1080
890
540
840
690
540
1080
890
540
1
900
740
450
—
—
—
900
740
450
042
0.50
1
/
2
4
1580
1290
790
1230
1010
790
1580
1290
790
3
1400
1150
700
1100
900
700
1400
1150
700
2
1230
1000
610
960
790
610
1230
1000
610
1
1050
860
530
—
—
—
1050
860
530
048
0.75
1
4
1730
1420
870
1350
1110
870
1850
1520
870
3
1550
1270
780
1210
990
780
1650
1350
780
2
1330
1090
670
1040
850
670
1430
1180
670
1
1120
920
560
—
—
—
1200
980
560
060
0.75
1
4
2050
1680
1030
1600
1310
1030
2280
1870
1030
3
1825
1500
910
1420
1170
910
2050
1680
910
2
1580
1300
790
1230
1010
790
1750
1430
790
1
1320
1080
660
—
—
—
1470
1210
660
070
0.75
1
4
2230
1780
1100
1710
1400
1100
2230
1780
1100
3
1950
1600
980
1520
1250
980
2100
1680
980
2
1700
1400
850
1330
1090
850
1840
1470
850
1
1450
1200
730
—
—
—
1520
1220
730
ESP — External Static Pressure