Carrier AQUAZONE PSV User Manual
Page 37

37
Table 22 — 50PSH, PSV, PSD012 Typical Unit Operating Pressures and Temperatures
LEGEND
Table 23 — 50PSH, PSV, PSD018 Typical Unit Operating Pressures and Temperatures
LEGEND
Table 24 — 50PSH, PSV, PSD024 Typical Unit Operating Pressures and Temperatures
LEGEND
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
FULL LOAD COOLING — WITHOUT HWG ACTIVE
FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5
98-108
140-160
36-41
14-19
17.1-19.1
19-25
72-82
301-321
9-14
12-17
6.5-8.5
21-27
2.25
98-108
135-155
36-41
12-17
12.5-14.5
19-25
85-95
304-324
9-14
12-17
4.7-6.7
21-27
3
99-109
127-148
36-41
10-15
7.9-9.9
19-25
78-88
308-328
9-14
12-17
2.9-4.9
22-28
50
1.5
118-128
215-235
22-27
14-19
18.1-20.1
20-26
100-110
337-357
10-15
15-20
9.5-11.5
26-32
2.25
118-128
200-220
22-27
12-17
13.1-15.1
20-26
98-108
334-354
10-15
15-20
6.6-8.6
26-32
3
118-128
185-205
22-27
10-15
8.1-10.1
19-25
95-105
332-352
11-16
15-20
3.8-5.8
26-32
70
1.5
132-142
300-320
11-16
12-17
17.0-19.0
19-25
115-125
361-381
19-24
18-23
11.1-13.1
29-35
2.25
132-142
263-282
11-16
10-15
12.6-14.6
19-25
112-122
360-380
20-25
18-23
8.0-10.0
29-35
3
132-142
245-265
12-17
7-12
8.2-10.2
19-25
110-120
356-376
21-26
18-23
4.8-6.8
29-35
90
1.5
138-148
366-386
9-14
11-16
15.8-17.8
18-24
122-132
376-396
34-39
22-27
12.1-14.1
32-38
2.25
138-148
353-373
9-14
9-14
14.9-16.9
18-24
123-133
378-398
36-41
22-27
9.0-11.0
32-38
3
138-148
340-360
9-14
6-11
14.0-16.0
18-24
124-134
380-400
38-43
23-28
5.8-7.8
32-38
110
1.5
145-155
453-473
9-14
9-14
14.7-16.7
16-22
—
—
—
—
—
—
2.25
145-155
442-462
9-14
7-12
10.8-12.8
16-22
—
—
—
—
—
—
3
145-155
431-451
9-14
5-10
6.8-8.8
17-23
—
—
—
—
—
—
DB
— Dry Bulb
HWG — Hot Water Generator
—
— No Heating Operation in This Temperature Range
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
FULL LOAD COOLING — WITHOUT HWG ACTIVE
FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5
120-130
155-175
27-32
11-16
16.9-19.9
16-22
73- 83
268-288
8-13
4- 9
6.1- 8.1
15-21
2.25
120-130
142-162
27-32
9-14
12.5-14.5
17-23
75- 85
270-290
8-13
4- 9
4.4- 6.4
16-22
3
120-130
128-148
27-32
9-14
8.1-10.1
17-23
78- 88
272-292
8-13
4- 9
2.9- 4.9
16-22
50
1.5
137-147
220-240
16-21
10-15
17.0-19.0
16-22
102-112
295-315
8-13
8-13
9.1-11.1
20-26
2.25
137-147
206-226
16-21
8-13
12.6-14.6
17-23
106-116
297-317
8-13
8-13
6.9- 8.9
21-27
3
137-147
192-212
16-21
8-13
8.4-10.4
17-23
110-120
299-319
8-13
8-13
4.7- 6.7
21-27
70
1.5
142-152
287-307
7-12
10-15
15.9-17.9
16-22
131-141
324-344
9-14
10-15
12.1-14.1
25-33
2.25
142-152
273-239
7-12
8-13
11.8-13.8
17-23
137-147
326-346
9-14
10-15
9.3-11.3
26-34
3
142-152
259-279
7-12
8-13
7.8- 9.8
17-23
144-154
328-348
9-14
10-15
6.6- 8.6
26-34
90
1.5
146-156
375-395
6-11
10-15
14.9-16.9
16-22
174-184
360-380
10-15
12-17
15.8-17.8
32-40
2.25
146-156
361-381
6-11
8-13
11.0-13.0
17-23
180-190
367-387
11-16
12-17
11.9-13.9
33-41
3
146-156
347-367
6-11
8-13
7.2- 9.2
17-23
187-197
374-394
12-17
12-17
8.0-10.0
33-41
110
1.5
154-164
478-498
6-11
10-15
14.0-16.0
16-22
—
—
—
—
—
—
2.25
154-164
461-481
6-11
8-13
10.2-12.2
16-22
—
—
—
—
—
—
3
154-164
445-465
6-11
8-13
6.5- 8.5
16-22
—
—
—
—
—
—
DB
— Dry Bulb
HWG — Hot Water Generator
—
— No Heating Operation in This Temperature Range
ENTERING
WATER
TEMP
(F)
WATER
FLOW
(GPM/ton)
FULL LOAD COOLING — WITHOUT HWG ACTIVE
FULL LOAD HEATING — WITHOUT HWG ACTIVE
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Rise
(F)
Air Temp
Drop
(F) DB
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Super-
heat
(F)
Sub-
cooling
(F)
Water
Temp
Drop
(F)
Air Temp
Rise
(F) DB
30
1.5
115-125
154-174
40-45
8-13
16.5-18.5
19-25
73- 83
283-303
8-12
6-11
5.9- 7.9
16-22
2.25
115-125
141-161
40-45
6-11
12.1-14.1
20-26
75- 85
285-305
8-12
6-11
4.2- 6.2
17-23
3
115-125
127-147
40-45
6-11
77.7- 9.7
20-26
78- 88
287-307
8-12
6-11
2.7- 4.7
18-24
50
1.5
115-120
209-229
24-29
10-15
15.7-17.7
18-24
102-112
313-333
8-12
8-13
8.9-10.9
22-28
2.25
115-120
195-215
24-29
8-13
11.6-13.6
18-24
106-116
314-334
8-12
8-13
6.7- 8.7
23-29
3
115-120
181-201
24-29
8-13
7.6- 9.6
18-24
110-120
316-336
8-12
8-13
4.5- 6.5
23-29
70
1.5
136-146
275-295
6-11
6-11
15.7-17.7
18-24
128-138
340-360
9-14
9-14
11.3-13.3
27-34
2.25
136-146
261-281
6-11
5-10
11.6-13.6
18-24
134-144
342-362
9-14
9-14
8.5-10.5
28-35
3
136-146
247-267
6-11
4- 9
7.6- 9.6
18-24
141-151
344-364
9-14
9-14
5.8- 7.8
28-35
90
1.5
140-150
361-381
6-11
6-11
14.9-16.9
18-24
162-172
370-390
14-19
9-14
14.4-16.4
32-40
2.25
140-150
347-367
6-11
5-10
11.0-13.0
18-24
166-176
376-396
15-20
9-14
10.8-12.8
34-42
3
140-150
333-353
6-11
4- 9
7.2- 9.2
18-24
171-181
383-403
16-21
9-14
7.1- 9.1
34-42
110
1.5
144-154
460-480
6-11
6-11
13.9-15.9
17-23
—
—
—
—
—
—
2.25
144-154
445-465
6-11
4- 9
10.2-12.2
17-23
—
—
—
—
—
—
3
144-154
428-448
6-11
4- 9
6.5- 8.5
17-23
—
—
—
—
—
—
DB
— Dry Bulb
HWG — Hot Water Generator
—
— No Heating Operation in This Temperature Range