Carrier AQUAZONE PSV User Manual
Page 26

26
Table 6 — 50PSH, PSV, PSD Electrical Data, ECM Motor
LEGEND
NOTES:
1. The 460-v units using an ECM (electronically commutated motor) fan
motor, modulating HWR, and/or an internal secondary pump will require
a neutral wire from the supply side in order to feed the accessory with
265-v.
2. Unit sizes 006-012 are not available with ECM motors.
50PS
UNIT
SIZE
RATED
VOLTAGE
V-Ph-Hz
VOLTAGE
MIN/MAX
COMPRESSOR
FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE/
HACR
UNITS WITH ECM MOTOR AND HWR
RLA
LRA
Qty
REHEAT
PUMP
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE /
HACR
018
208/230-1-60
197/254
9.0
48.0
1
4.3
13.3
15.6
20
0.8
14.1
16.4
25
265-1-60
239/292
8.4
40.0
1
4.1
12.5
14.6
20
0.7
13.2
15.3
20
024
208/230-1-60
197/254
12.8
60.0
1
4.3
17.1
20.3
30
0.8
17.9
21.1
30
208/230-3-60
197/254
8.0
55.0
1
4.3
12.3
14.3
20
0.8
13.1
15.1
20
460-3-60
414/506
4.0
22.4
1
4.1
8.1
9.1
15
0.7
8.8
9.8
15
030
208/230-1-60
197/254
13.5
61.0
1
4.3
17.8
21.2
30
0.8
18.6
22.0
35
265-1-60
239/292
10.9
58.0
1
4.1
15.0
17.7
25
0.7
15.7
18.4
25
208/230-3-60
197/254
8.3
63.0
1
4.3
12.6
14.7
20
0.8
13.4
15.5
20
460-3-60
414/506
4.5
27.0
1
4.1
8.6
9.7
15
0.7
9.3
10.4
15
036
208/230-1-60
197/254
14.7
72.5
1
4.3
19.0
22.7
35
0.8
19.8
23.5
35
265-1-60
239/292
12.5
61.0
1
4.1
16.6
19.7
30
0.7
17.3
20.4
30
208/230-3-60
197/254
10.4
63.0
1
4.3
14.7
17.3
25
0.8
15.5
18.1
25
460-3-60
414/506
4.5
32.0
1
4.1
8.6
9.7
15
0.7
9.3
10.4
15
042
208/230-1-60
197/254
15.4
83.0
1
4.3
19.7
23.6
35
0.8
20.5
24.4
35
208/230-3-60
197/254
11.5
77.0
1
4.3
15.8
18.7
30
0.8
16.6
19.5
30
460-3-60
414/506
5.1
35.0
1
4.1
9.2
10.5
15
0.7
9.9
11.2
15
048
208/230-1-60
197/254
20.5
109.0
1
7.0
27.5
32.6
50
1.07
28.6
33.7
50
208/230-3-60
197/254
14.6
91.0
1
7.0
21.6
25.3
35
1.07
22.7
26.3
40
460-3-60
414/506
7.1
46.0
1
6.9
14.0
15.8
20
1.07
15.1
16.8
20
060
208/230-1-60
197/254
26.9
145.0
1
7.0
33.9
40.6
60
1.07
35.0
41.7
60
208/230-3-60
197/254
17.6
123.0
1
7.0
24.6
29.0
45
1.07
25.7
30.1
45
460-3-60
414/506
9.6
64.0
1
6.9
16.5
18.9
25
1.07
17.6
20.0
25
070
208/230-1-60
197/254
30.1
158.0
1
7.0
37.1
44.6
70
1.07
38.2
45.7
70
208/230-3-60
197/254
20.5
155.0
1
7.0
27.5
32.6
50
1.07
28.6
33.7
50
460-3-60
414/506
9.6
75.0
1
6.9
16.5
18.9
25
1.07
17.6
20.0
25
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
HWR
— Hot Water Reheat
LRA
— Locked Rotor Amps
RLA
— Rated Load Amps
COMPLETE C CONTROL
ECM CONTROL
BOARD
CAPACITOR
LINE
LOAD
COMPRESSOR CONTACTOR
TRANSFORMER
Fig. 26 — 50PSH,PSV,PSD Typical Single-Phase Line Voltage Power Connection
A50-7737